CPS Models
Input
Nominal voltage
Nominal frequency
Accepted input voltage tolerance due to no
intervention of the battery (referred to 400Vac)
Accepted input frequency tolerance due to no
intervention of the battery (referred to 50/60Hz)
Cut-in threshold in Emergency Only mode and
for EOS
Cut-in time in Emergency Only mode
Input current harmonic distortion
Input power factor
Power Walk-in
Output
(1)
Nominal voltage
(2)
Nominal frequency
Nominal apparent output power
Nominal active output power
Output power factor
Short circuit current
Precision of output voltage (referred to output
voltage of 400Vac)
(3)
Static stability
Dynamic stability
Voltage harmonic distortion with linear and
normalised distorting load
Crest factor allowed with nominal load
Frequency precision in free running mode
Inverter overload (Vin>345V AC )
Bypass Overload
Battery Charger
Nominal voltage
Maximum recharge current
Input voltage tolerance for recharging at
maximum current

TECHNICAL DATA

380-400-415 Vac 3-phase with neutral (4 wire) / 220-230-240 Vac single phase
(5)
CPS 6
CPS10
50-60Hz
20% @ 100% load
-40% +20% @50% load
40-72Hz
- 20% of nominal voltage
< 300ms
THDi  3%
Programmable from 1 to 125 sec. in steps of 1 sec.
220/230/240 Vac single phase
50/60Hz
6 kVA
5.4 kW
1.5x In for t>500ms
 0.5%
 3% resistive load
1% with linear load
3% with distorting load
120% Infinite, 130% 10 min, 160% 1 min
130% Infinite,160% 60 minutes, 180% 10 minutes
240Vdc
345-480Vac
- 114 -
CPS 15
20%
(7)
≥0.99
10kVA
15kVA
9kW
13.5kW
0.9
 1%
(4)
3:1
0.01%
6A