Herunterladen Inhalt Inhalt Diese Seite drucken

Led Keypad (Item No. 013000) As Master - Honeywell 041460.17 Montage- Und Bedienungsanleitung

Tagalarm-plus konventionell
Vorschau ausblenden Andere Handbücher für 041460.17:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting and Operating Instructions Doorguard hardwired version
5.1.12

LED keypad (Item no. 013000) as master

Only the LED keypad (Item no. 013000) is alternatively possible to set to master function.
Advantage:
! All Doorguard devices have a own address (15 piece, no double addressing). This consists a easier way
to identify.
! The colors of LED´s are the same at the Doorguard and at the LED keypad:
Red shows a alarm trigger, green shows a door lock release and yellow shows a fault.
! Start setting the address at the Doorguard slaves with address 1 in ascending order, (max. to address 15).
! Configurate all Doorguard devices to slave, that means DIP switch S8 = OFF.
! Set LED keypad to the highest (last) Doorguard address of the network.
! The LED keypad is parameterized to master function as follows:
- DIP switch of LED keypad, S8 = ON.
- Then press key 10 (left colum at the bottom) and now switch on the operating voltage to the
LED keypad (pin up the plugable terminal).
- The green LED assigned to key 10 flashes with a frequency of 1Hz. 8 yellow LED's lights up on
the right side of the column.
- Press key 12 - activation of master function. (Second key from the top, on the right side of the
column).
- The red LED assigned to key 12 shows master functon. (Master ON/OFF in toggle).
- DIP switch S8 = OFF. Parametriermode is switched off. After 2 seconds the LED keypad is ready.
- The LED keypad is now master.
! When the yellow LED at the LED keypad flashes following error might occur: not available network users,
wrong setting of network addresses or a wrong setting of DIP switch S8 at the Doorguard.
Hint: If the LED keypad set to operating voltage whithout a master function programming, the green
LED top left lights up and after 20 seconds a acoustical message appear - that means "no BUS
function". This message can be canceled by pressing a key, but the programming must be repeated.