Table I: Operating limits
Minimum ambient temperature:
Mains power supply
The Head Pressure Controller (HPC) is composed of two parts:
-
Electronic board
-
Temperature sensor
The temperature sensor is mounted on the outdoor battery.
The signal transmitted by the sensor is processed by the electronic board placed inside the control panel, which controls the outdoor fan(s) supply voltage.
The Head Pressure Controller is operating in cooling mode only; therefore, in the heat pump units the reversing valve signal must be transmitted to the electronic
board so that the controller can recognize that it is operating in heating mode.
To help start-up, the fan is operated at full voltage for 3" at each compressor start-up, regardless of the battery temperature (HARD START function).
Tabella I: Limiti di funzionamento
Temperatura minima ambiente
Alimentazione elettrica
Il controllo di condensazione "HPC" è composto da 2 parti:
-
Scheda elettronica
-
Sensore di temperatura
Il sensore di temperatura è posizionato sulla batteria esterna.
La scheda elettronica, posizionata all'interno del quadro elettrico, elabora il segnale del sensore, controllando la tensione di alimentazione del (dei) ventilatore (i) esterni.
Il controllo di condensazione è attivo solo in modo raffrescamento, quindi sulle unità pompa di calore è necessario portare alla scheda elettronica il segnale della
valvola d'inversione, affinché il controllo riconosca il funzionamento in riscaldamento.
Per favorirelo spunto, il ventilatore viene alimentato alla tensione piena per 3" ad ogni spunto del compressore, indipendentemente dalla temperatura di batteria
(funzione HARD START).
Kit components
(fig. page 1)
Ref Q.ty Description
1
Crankcase heater
Fan speed controller
1
electronic card
3
Electric cables
2+2 Card fixing clips
4
Nylon strips
1
Wiring diagram
1
Warning label
1
Clip
Temperature sensor
1
with cables
Crankcase heater
3
tension spring
1
Installation instructions
Head pressure controller for monosplit cooling
only, heat pump and multisplit cooling only.
The kit task is to keep head pressure steady while
outdoor ambient temperature decreases as
outdoor unit fan motor speed does.
-15 °C 38GL / 38YY
-10 °C 38GL2M / 38GL3M / 38GL4M
Nominal voltage 230 V - 50 Hz
Operating voltage limits min. 198 V – max. 264 V
-15 °C 38GL / 38YY
-10 °C 38GL2M / 38GL3M / 38GL4M
Tensione nominale 230 V - 50 Hz
Limiti di tensione
2
Componenti del kit
(fig. pag. 1)
Ref Q.tà Descrizione
1
Riscaldatore del carter
Scheda elettronica regolatore
1
di velocità
3
Cavi elettrici
Clips fissa-scheda
2+2
4
Fascette nylon
1
Schema elettrico
1
Targhetta avvertenze
1
Clip
Sensore temperatura
1
completo di cavi
Molla tensionamento
3
riscaldatore del carter
1
Istruzioni di installazione
Controllo di condensazione per monosplit
solo raffrescamento, pompa di calore e
multisplit solo raffrescamento.
II kit ha la funzione di mantenere costante la
temperatura di condensazione all'abbassarsi
della temperatura ambiente esterno,
diminuendo la velocità del motore del ventilato-
re posto nell'unità esterna.
min. 198 V – max. 264 V