Fronius Primo serie Serviceanleitung, Ersatzteilliste Seite 96

Netzgekoppelter wechselrichter
Vorschau ausblenden Andere Handbücher für Primo serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
102
Grid voltage above permis-
sible limits
103
Grid voltage below permis-
sible limits
105
Grid frequency above per-
missible limits
106
Grid frequency below per-
missible limits
107
Synchronization with public
grid supplier not possible
108
Stand-alone operation de-
tected
96
Behavior
1. Grid voltage error
2. Incorrect values in service
menu; incorrect setup
3. Bad contact: wall bracket <-
-> filter PC board
1. Grid voltage error
2. Incorrect AC cabling
3. Incorrect values in service
menu; incorrect setup
4. Bad contact: wall bracket <-
-> filter PC board
5. Measurement error on filter
PC board
1. Grid frequency error
2. Incorrect values in service
menu; incorrect setup
3. Recombination limit reached
4. Round control signals
5. Measurement error on filter
PC board
1. Grid frequency error
2. Incorrect values in service
menu; incorrect setup
3. Round control signals
4. Measurement error on filter
PC board
1. Incorrect values in service
menu; incorrect setup
2. Bad contact: power module
with AC
3. Bad AC connection
4. Measurement error on filter
PC board
1. Stand-alone operation de-
tected
2. Severe disruption on the
public grid
3. Bad contact: wall bracket <-
-> filter PC board
4. Grid impedance outside of
permissible range
5. Bad AC connection
6. Round control signals
7. Measurement error on filter
PC board
Remedy
1. Check grid voltage
2. Check values in service
menu and setup
3. Replace filter PC board
1. Check grid voltage
2. Check AC cabling
3. Check values in service
menu and setup
4. Check fixing screws in DAT-
COM area
5. Replace filter PC board
1. Check grid frequency
2. Check values in service
menu and setup
3. Normal statutory require-
ment, no error (50.05 Hz)
4. Message to Fronius Techni-
cal Support specialists
5. Replace filter PC board
1. Check grid frequency
2. Check values in service
menu and setup
3. Message to Fronius Techni-
cal Support specialists
4. Replace filter PC board
1. Check values in service
menu and setup
2. Check AC connection
screws
3. Check grid connection
4. Replace filter PC board
1. Automatic correction
2. Automatic correction
3. Check fixing screws in DAT-
COM area
4. Contact energy provider
5. Check AC connection
6. Message to Fronius Techni-
cal Support specialists
7. Replace filter PC board