Fronius Primo serie Serviceanleitung, Ersatzteilliste Seite 102

Netzgekoppelter wechselrichter
Vorschau ausblenden Andere Handbücher für Primo serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
462
Error detected when moni-
toring DC deceleration
463
AC pole reserved
472
Fuse for solar module
ground faulty
474
RCMU sensor fault
475
Insulation fault detected
476
Internal power supply miss-
ing
480
Power module and display
software incompatible
481
Recerbo has old software
version
482
Inverter switched off during
commissioning
483
Set DC2 fixed voltage out-
side of the permitted MPP
range
484–485
Error during data transfer
102
Behavior
1. Occurs once
2. Monitoring of DC decelera-
tion faulty
1. AC connection between
power module and filter PC
board established in incorrect
direction (L1 and L2 mixed up)
1. Faulty fuse for solar module
ground
2. Incorrect setting in basic ser-
vice menu
1. Quick irradiation change
2. Sensor faulty
1. Incorrect setting
2. Grounding fault PV genera-
tor
3. Measurement circuit on
power module defective
1. Grid voltage too low
2. Grid test time is too low
3. Missing internal power sup-
ply
4. Missing internal power sup-
ply
1. Old power module/display
software
2. Old software
3. Incompatible hardware com-
bination
1. Old Recerbo software
2. Old software
3. Incompatible hardware com-
bination
1. Startup process not suc-
cessful
1. Incorrectly set fixed voltage
1. Communication problem
caused by temporary environ-
mental faults (grid, EMC, etc.)
2. Ribbon cable between filter
PC board and power module
faulty
3. Faulty AC guard on filter PC
board
4. Faulty AC guard on power
module
Remedy
1. Restart inverter
2. Replace inverter
1. Check cabling
1. Replace fuse
2. Set DC mode to "floating"
1. Automatically corrected
2. Replace filter PC board
1. Check ISO/GFDI setting
2. Check PV generator
3. Replace DC PC board and
then, if necessary, AC PC
board
1. Check cabling
2. Grid failure
3. Replace AC PC board
4. Replace filter PC board
1. Software update
2. Reload setup
3. Check hardware compo-
nents
1. Software update
2. Reload setup
3. Check hardware compo-
nents
1. Restart inverter
1. Check settings
1. Automatically corrected
2. Replace ribbon cable
3. Replace filter PC board
4. Replace AC PC board