Step 3: Wire the HVAC signals and power supply
Using the diagram on the previous page and the appropriate wiring diagram below, connect the power 
supply and fan coil unit to the FCU controller. Wire harnesses can be extended using 18 AWG or 
22 AWG (1.0 mm
 or 0.5 mm
) wire. Use twisted pair, shielded cables to extend analog I / O and FCU 
2
2
controller links. All terminal blocks are removable. For color diagrams, see the myRoom Fan Coil Unit
Controller specification submittal (P/N 3691082) on www.lutron.com.
Wire Type
AWG
24 to 14
22 to 14
Wire
Size
mm
2
0.2 to 2.5
0.25 to 2.5
Wiring Diagram 1 (fan coil unit)
2-pipe system, On / off valve, 3-speed fan, changeover sensor
Valve
5
R
6
VALVE
R
7
FAN
G
8
3
9
G
2
10
G
1
11
12
Controller power*
4 G 3 5
Wiring Diagram 2 (fan coil unit)
4-pipe system, On / off valve, 3-speed fan
H
5
VALVE
R
6
H
R
7
FAN
G
8
3
G
9
2
10
G
1
11
C
VALVE
12
R
C
Controller power*
4 G 3 5
*    I f the signal source from the fan coil unit is not 24 V~, use a separate supply to power the  
FCU controller.
**    S ensor is optional. Semitec 103AT or equivalent – NTC 10 k at 25 °C.
    A  Class 2/LPS transformer should be used. The transformer should be rated to supply the power 
drawn by external circuits as well as the controller.
   R ated for 1.25 A.
L1 (Line/Hot) voltage of 120 – 240 V~ is acceptable.
‡‡
WARNING: Fire/Shock Hazard. May result in serious injury or death. Use a Class 2 or 
Limited Power Source (LPS) transformer. Install a fuse sized to the total load (controller 
and I/O) on the secondary of the transformer, but no more than the equivalent capacity of 
a Class 2 or LPS circuit if such a transformer is unavailable. 

Important Notes

•    E ach inductive load, driven by the relay contacts, must include a suppression device such as a 
peak limiter, RC circuit or fly‐back diode to extend relay life.
•    D o not connect relay outputs to capacitive loads. 
•    I mproperly sized or otherwise incorrect circuit‐breakers or fuses may allow excessive current 
beyond the capacity of the controller.
Lutron and Palladiom are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. 
myRoom is a trademark of Lutron Electronics Co., Inc.
®
2 x 
2 x 
24 to 18
24 to 16
2 x 
2 x 
0.2 to 1.0
0.2 to 1.5
4.4 to 5.3 in-lb
 (0.5 to 0.6 N•m)
24 V~  
transformer   
Valve
by others
24 V~
Fan high
Common
Fan medium
Fan low
Fan Control Board
Type T 
Fuse
Common
Changeover sensor**
24 V~  
transformer   
Hot valve
by others
24 V~
Fan high
Common
Fan medium
Fan low
Cold valve
Fan Control Board
Type T 
Fuse
Common
Step 4: Basic Configuration Instructions
The FCU controller must be correctly configured for the fan coil unit. The Palladiom thermostat is 
used to configure the FCU controller. The thermostat must be connected to the FCU controller and 
both must be powered to set a configuration.
WARNING: Shock Hazard. Improper configuration can cause property damage, personal 
injury, or death. Installation and service must be performed by a licensed professional HVAC 
installer (or equivalent) or service agency. 
1.   D etermine the basic configuration number of the system using the table below.
System
2 x 
2 x 
Configuration
22 to 18
20 to 16
(Pipe
Configuration)
2 x 
2 x 
0.25 to 1.0
0.5 to 1.5
As-is
•   4 -pipe
•   2 -pipe cooling 
with resistive 
heating 
element
•   2 -pipe heating 
only
•   2 -pipe cooling 
only
•   2 -pipe with a 
changeover 
sensor
2. Enter basic configuration mode.
L1
‡‡
a.   I f the thermostat has been powered for over 15 minutes, cycle power to the thermostat. See 
(Line/Hot)
the Palladiom Configuration Instructions Install (041563) at www.lutron.com. The previously 
saved configuration is restored after a  power cycle.
L2 
b.   H old the 
C
(Neutral)
buttons and hold only the 
c.   T he thermostat will enter basic configuration mode, with "Set" and one circle filled in on the 
display.
Hold 3 seconds to save and exit 
configuration mode.
L1
‡‡
(Line/Hot)
3. Set basic configuration mode.
a.   O nce in basic configuration mode, Tap the } or { buttons to display the desired 
configuration number found in the table above. Only the supported options are displayed.
L2 
(Neutral)
b.   H old the  u button for 3 seconds to save this configuration. The display will flash, then normal 
operation will begin.
4.   A dvanced configuration mode.
a.   T o modify optional advanced configuration parameters, see the Palladiom Configuration
Instructions Install (P/N 041563) at www.lutron.com

Troubleshooting

Symptom
Controller not on (green LED on bottom of 
unit not on).
Lutron Customer Assistance:
U.S.A. / Canada: 1.844.LUTRON1 (588.7661)
Mexico: 1.888.235.2910
Europe: +44.(0)20.7680.4481
Asia: 800.120.4491
Other: +1.610.282.3800
www.lutron.com/support
Eliwell Controls s.r.l.
Via dell'Industria, 15 • Zona Industriale Paludi • 32010 Pieve d'Alpago (BL) ITALY
T +39 0437 986 111 | T +39 0437 986 100 (Italy) | +39 0437 986 200 (other countries)
E saleseliwell@schneider-electric.com | Technical helpline +39 0437 986 300
E techsuppeliwell@schneider-electric.com | www.eliwell.com
FCU Controller – MADE IN ITALY
03/2018 © Eliwell Controls s.r.l. 2018 All rights reserved.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of 
this material.
Valve / Element
Fan Control
Control
(Fan Type)
(Valve Type)
Use current configuration on the controller
Two on / off relays
H / M / L relays
One on / off relay
H / M / L relays
Set
Set
Set
C
F
F
 and 
 buttons for 3 seconds. Once the display begins to flash, release both 
C
F
 button for 3 seconds.
C
F
Set
Set
C
Hold 
 and 
 for 3 seconds,then 
C
F
 for 3 seconds to enter mode.
C
F
Probable Cause
Controller is not receiving power. Confirm that the 
Red and Red / Gray wires are connected to the power 
supply as specified in the present document.
2-pipe / Single
Basic
Thermal Type
Configuration
(2-pipe mode)
Number
00
01
Changeover 
05
Sensor
Heat only
06
Cool only
07
Set
Increase
Set
Decrease
F

Werbung