Step 3: Wire the HVAC signals and power supply
Using the diagram on the previous page and the appropriate wiring diagram below, connect the power
supply and fan coil unit to the FCU controller. Wire harnesses can be extended using 18 AWG or
22 AWG (1.0 mm
or 0.5 mm
) wire. Use twisted pair, shielded cables to extend analog I / O and FCU
2
2
controller links. All terminal blocks are removable. For color diagrams, see the myRoom Fan Coil Unit
Controller specification submittal (P/N 3691082) on www.lutron.com.
Wire Type
AWG
24 to 14
22 to 14
Wire
Size
mm
2
0.2 to 2.5
0.25 to 2.5
Wiring Diagram 1 (fan coil unit)
2-pipe system, On / off valve, 3-speed fan, changeover sensor
5
Valve
R
6
VALVE
7
R
FAN
8
G
3
9
G
2
10
G
1
11
12
AO
4
G
3
5
Wiring Diagram 2 (fan coil unit)
4-pipe system, On / off valve, 3-speed fan
H
5
VALVE
R
6
H
7
R
FAN
8
G
3
9
G
2
10
G
1
C
11
VALVE
12
R
C
AO
G
4
3
5
* Sensor is optional. Semitec 103AT or equivalent – NTC 10 k at 25 °C.

Important Notes

• Each inductive load, driven by the relay contacts, must include a suppression device such as a
peak limiter or RC circuit to extend relay life.
• Do not connect relay outputs to capacitive loads.
• Improperly sized or otherwise incorrect circuit‐breakers or fuses may allow excessive current
beyond the capacity of the controller.
Lutron, myRoom, and Palladiom are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the
US and/or other countries.
®
2 x
2 x
2 x
24 to 18
24 to 16
22 to 18
2 x
2 x
2 x
0.2 to 1.0
0.2 to 1.5
0.25 to 1.0
4.4 to 5.3 in-lb
(0.5 to 0.6 N•m)
Valve
Valve In (24 V~ / 100 V~ / 120 V~ / 220-240 V~)
Fan In (24 V~ / 100 V~ / 120 V~ / 220-240 V~)
Fan High
Fan Medium
Fan Low
Controller Power
Listed Class 2, LPS, or SELV limited
energy supply <15 W
12–24 V~ / 24 V-
Common
Changeover sensor*
Hot Valve
Hot Valve In (24 V~ / 100 V~ / 120 V~ / 220-240 V~)
Fan In (24 V~ / 100 V~ / 120 V~ / 220-240 V~)
Fan High
Fan Medium
Fan Low
Cold Valve
Cold Valve In (24 V~ / 100 V~ / 120 V~ / 220-240 V~)
Controller Power
Listed Class 2, LPS, or SELV limited
energy supply <15 W
12–24 V~ / 24 V-
Common
Step 4: Basic Configuration Instructions
The FCU controller must be correctly configured for the fan coil unit. The Palladiom thermostat is
used to configure the FCU controller. The thermostat must be connected to the FCU controller and
both must be powered to set a configuration.
1. Determine the basic configuration number of the system using the table below.
System
Valve / Element
Configuration
Control
(Pipe
(Valve Type)
Configuration)
2 x
As-is
Use current configuration on the controller
20 to 16
• 4-pipe
2 x
• 2-pipe cooling
0.5 to 1.5
with resistive
Two on / off relays
heating
element
• 2-pipe heating
only
• 2-pipe cooling
only
One on / off relay
• 2-pipe with a
changeover
sensor
2. Enter basic configuration mode.
a. If the thermostat has been powered for over 15 minutes, cycle power to the thermostat. See the
Palladiom Configuration Instructions (P/N 041563) at www.lutron.com. The previously saved
configuration is restored after a power cycle.
b. Hold the
C
F
and
buttons and hold only the
c. The thermostat will enter basic configuration mode, with "Set" and one circle filled in on the
display.
Hold 3 seconds to save and exit
configuration mode.
3. Set basic configuration mode.
a. Once in basic configuration mode, Tap the } or { buttons to display the desired
configuration number found in the table above. Only the supported options are displayed.
b. Hold the u button for 3 seconds to save this configuration. The display will flash, then normal
operation will begin.
4. Advanced configuration mode.
a. To modify optional advanced configuration parameters, see the Palladiom Configuration
Instructions (P/N 041563) at www.lutron.com

Troubleshooting

Symptom
Controller not on (green LED on bottom of
unit not on).
Lutron Customer Assistance:
U.S.A. / Canada: 1.844.LUTRON1 (588.7661)
Mexico: 1.888.235.2910
Europe: +44.(0)20.7680.4481
Asia: 800.120.4491
Other: +1.610.282.3800
www.lutron.com/support
Eliwell Controls s.r.l.
Via dell'Industria, 15 • Zona Industriale Paludi • 32010 Pieve d'Alpago (BL) ITALY
T +39 0437 986 111 | T +39 0437 986 100 (Italy) | +39 0437 986 200 (other countries)
E saleseliwell@schneider-electric.com | Technical helpline +39 0437 986 300
E techsuppeliwell@schneider-electric.com | www.eliwell.com
FCU Controller – MADE IN ITALY
10/2019 © Eliwell Controls s.r.l. 2018 All rights reserved.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of
this material.
2-pipe / Single
Fan Control
Thermal Type
(Fan Type)
(2-pipe mode)
H / M / L relays
Changeover
Sensor
H / M / L relays
Heat only
Cool only
Set
Set
Set
C
F
buttons for 3 seconds. Once the display begins to flash, release both
C
F
button for 3 seconds.
Set
C
F
Set
Set
Set
C
F
Hold
and
for 3 seconds,then
C
F
for 3 seconds to enter mode.
C
F
Probable Cause
Controller is not receiving power. Confirm that the
Red and Red / Gray wires are connected to the power
supply as specified in the present document.
Basic
Configuration
Number
00
01
05
06
07
Increase
Decrease