Program group P2
Program group P2 is intended for additional thermostat's settings.
In program group P2 are the following parameters;
(factory setting):
- [P2.1] Domestic hot water temperature (20 °C ÷ 80°C); (55 °C)
- [P2.2] Switch-on hysteresis for domestic hot water
(0.5 °C ÷ 10 °C); (4°C)
- [P2.3] Minimal boiler temperature (20 °C ÷ 70 °C); (50 °C)
- [P2.4] Maximal boiler temperature (50 °C ÷ 97 °C); (90 °C)
- [P2.5] Naximal stand-pipe temperature (25 °C ÷ 95 °C); (65 °C)
- [P2.6] Maximal floor temperature (10 °C ÷ 40 °C); (30 °C)
- [P2.7] Beeper mode (- - - silent, 1 - by typing, 2 - by program
Timer changeover, 3 - by typing and program timer
changeover); (1)
- [P2.8] Radio channel number (1 ÷ 16); (1)
- [P2.9] Radio module type (1 - AM module, 2 - FM module); (1)
- [P2.10] Display of measured temperatures (1 - built in sensor,
2 - auxiliary sensor, 3 - both sensors - alternating,
4 - display of requested (setted) temperature,
5 - return-pipe temperature sensor); (1)
- [P2.11] Actuator speed (1 ÷ 8 min); (2 min)
- [P2.12] Tvmin in cooling mode (10 ÷ 24 °C); (16 °C)
Program group P3
Program group P3 is intended to set the remote control with tele-
phone. In program group P3 are the following parameters; (factory
setting):
- [P3.1] Requested temperature (10 °C ÷ 30 °C, P - temperature
setted with the knob); (P)
27