Program group P1
Program group P1 is used for the thermostat user settings. To
change the selected parameter, hold key
seconds. Parameter starts to flash. Press key
to set the parameter value. To store the setted value, again hold
key
for approximately 5 seconds.
i i i i
This procedure, for modifying the parameter, is the same for all program
and service groups.
Group P1 contains the following parameters; (factory setting):
- [P1.1] Night temperature (6 °C ÷ 26 °C); (17 °C)
- [P1.2] temp. reduction in ECO mode (0 °C ÷ -9 °C); (-3 °C)
- [P1.3] frost protection temperature (2 °C ÷ 20 °C,
- - - deactivated, P - temp. is setted with the knob); (6 °C)
- [P1.4] holiday mode temperature (5 °C ÷ 25 °C); (12 °C)
- [P1.5] ED constant (5 min ÷ 50 min, - - - deactivated); (20 min)
- [P1.6] Display of controlled device (- - - none, 1 - oil boiler,
2 - gas boiler, 3 - actuator, 4 - pump); (1)
- [P1.7] Temperature sensor calibration (-2 °C ÷ 2 °C); (6 °C)
- [P1.8] Comfort mode temp. (10 °C ÷ 30 °C, - - - inactive); (- - -)
- [P1.9] Periodic activation of pumps and mixing valve
(- - - deactivated, 1 - activated)
1
Activation is every Saturday at:
21:01 - mixing valve or circulation pump activation
21:02 - d. h. w. circulation pump activation
Settings manual
1
; (1)
26
for approximately 5
(
) or
(
)