Herunterladen Inhalt Inhalt Diese Seite drucken

General Installation Data; Applications; Potentially Explosive Environments; Identification - Grundfos IO 112 Montage- Und Betriebsanleitung

Messmodul
Vorschau ausblenden Andere Handbücher für IO 112:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 17

2.1 General installation data

Supply voltage:
Supply current:
Power consumption:
Ambient temperature:
Enclosure class:
Check that the supply voltage corre-
sponds to the values stated on the name-
plate: 24 VAC 50/60 Hz /24 VDC ±10%.
Min. 2.4 A.

3. Applications

By means of the IO 112 it is possible to
• monitor and control the liquid level
• monitor and control the temperature
• use the counter function, for instance if the pump
is to pump a specific volume and then stop.
IO 112 must not be used for other pur-
poses as the ones specified.

3.1 Potentially explosive environments

IO 112 must not be installed in explosive environ-
ments, but may be used together with Grundfos
pumps approved for installation in potentially explo-
sive environments.

4. Identification

4.1 Nameplate

The nameplate is fitted on the side of IO 112.
1
Type
IO
112
Product no.
2
96177804
24Vac 50/60Hz, 24 VDC
U
N
3
P
5W
max.
4
Made in Denmark
Fig. 2
Nameplate
Pos.
Description
1
Type designation
2
Product number
3
Rated voltage
4
Power
5
Version number
6
Serial number
7
Production code (year and week)
8
Enclosure class
24 VAC ±10% 50/60 Hz
24 VDC ±10%
Min. 2.4 A; max. 8 A
Max. 5 W
–25°C to +65°C
IP 20
5
6
7
V-
V01
P.c.
0630
NB
Serial no.
8
20
IP

4.2 Type key

Code Meaning
IO
Input/output unit
1
Simple complexity
1
Controller series
2
Model number

5. Storage

IO 112 may be stored for maximum two years.
See date on the box label.

6. Installation

Before installation, check that the
• IO module is the one ordered.
• IO 112 is suitable for the supply voltage and fre-
quency available at the installation site.
• IO 112 has not been damaged during transporta-
tion.
Before installing the IO 112, make sure
that the electricity supply has been
switched off and that it cannot be acciden-
tally switched on.
The installation must be carried out by authorized
personnel in accordance with local regulations.
All safety regulations must be observed on the instal-
lation site.

6.1 Location

IO 112 is only for indoor installation.
IO 112 must not be installed in potentially
explosive environments. Ex-approved
pumps may, however, be installed in an
explosive environment.
Enclosure class
IO 112 is enclosure class IP 20 and designed
according to overvoltage and measurement category
II. In order to reduce the external pollution level to
maximum 2, the IO 112 must be installed in a pro-
tecting environment with minimum IPX4 enclosure
according to IEC 60529. The cabinet must be of a
flame-retardant material.
Ambient temperature
–25°C to +65°C.
IO 112 must not be exposed to direct sunlight.
Installation height
Maximum 2000 m above sea level.
Relative air humidity
Maximum 95%.
IO
1
1
2
5

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis