4.5

Workflow diagram for commissioning the SED1

D is p lay P ara m eters
S elec t D is p la y via
P ar a m e te r 0 01
in the E xp er t
P ar a m e te r M o d e.
D is play fre q uenc y .
P ar a m e te r 0 01
0 = O utput fr e que nc y
D is play m oto r c urr e nt.
P ar a m e te r 0 01
2 = M oto r c ur re nt
D is play m oto r s p ee d .
P ar a m e te r 0 01
5 = M oto r s p ee d (R P M )
30/62
Siemens Building Technologies
Landis & Staefa Division
C o m m is io n in g
S E D 1
B as ic P aram eters
R a m p -up tim e .
P a ra m ete r 0 0 2
0 - 15 0 s ec
R a m p -d o w n tim e .
P a ra m ete r 0 0 3
0 - 15 0 s ec
D ig it. fre q . s e tpo int.
P a ra m ete r 0 0 6
0= m anua l s etp o int
1= a nalo g / 2 = d ig ita l s e tup
Ha nd/A uto .
P a ra m ete r 0 0 7
0 = Hand
1 = A uto
M inim um m o tor fr e q.
P a ra m ete r 0 1 2
0 - 1 5 0 Hz
M a xim um m o to r fr eq .
P a ra m ete r 0 1 3
0 - 1 5 0 Hz
S tar t on the F ly .
P a ra m ete r 0 1 6
0= d is ab le 2= ena b le
No m ina l r ating plate
fr e que nc y fo r m o to r .
P a ra m ete r 0 8 1
0 - 1 5 0 Hz
No m ina l r ating plate
s pe e d fo r m oto r.
P a ra m ete r 0 8 2
0- 9 99 9 U/m in
No m ina l r ating plate
c urr ent for m o tor .
P a ra m ete r 0 8 3
0,1 - 5 90 A
No m ina l r ating plate
vo lta g e fo r m oto r.
P a ra m ete r 0 8 4
0 - 1 0 0 0V
No m ina l r ating plate
po w e r for m o to r.
P a ra m ete r 0 8 5
0,1 2 - 40 0 kW
E na ble E xp e rt p ar a .
P a ra m ete r 1 9 9
0= B a s ic pa r am e te r
1= E xp e rt p ar am e ter
SED1-Frequenzumrichter
Workflow diagram for commissioning the SED1
E x p ert P aram eters
A uto m a tic re s tar t
a fte r m a ins fa ilur e.
P a ra m e te r 0 1 5
0 = d is p la y / 1= e nab le
A uto m a tic re s tar t a fte r
fault.
P a ra m e te r 0 1 8
0 = d is a ble / 1= ena b le
A na lo gue inp ut.
P a ra m e te r 0 2 3
0 = 0- 1 0V / 0 -2 0 m A
1 = 2- 1 0V / 4 -2 0 m A
S k ip fre q ue nc y .
P a ra 0 14 /0 27 /02 8 /02 9
0 - 15 0 Hz
Input te r m inal func tion.
P a ra m e te r 0 5 1- 0 56
s e e tab le
S e le c tion r ela y o utp ut.
P a ra m e te r 0 6 1 & 0 6 2
s e e tab le
D C inje c tion b ra k ing .
P a ra m e te r 0 7 3
0 - 20 0 %
P uls e fr e que nc y .
P a ra m e te r 0 7 6
s e e tab le
M o to r c urr e nt lim it.
P a ra m e te r 0 8 6
0 - 20 0 %
Fo r fur the r
E xp e rt P a ra m ete rs
s e e the
P r ojec t hand b oo k
CM1U5191X
01.2000