Herunterladen Inhalt Inhalt Diese Seite drucken

YASKAWA GA500 Serie Installations- Und Bedienungansleitung Seite 272

Vorschau ausblenden Andere Handbücher für GA500 Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 38
10 Attachment
Input/Output
Serial communication input/output
24 V external power supply
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric
Code (NEC) and the Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and L1-01 through L1-04 [Motor Overload Protection Select]
correctly to enable motor overload and overheat protection.
Refer to the control method and set the motor rated current with E2-01 [Motor Rated Current
(FLA)], E5-03 [PM Motor Rated Current (FLA)], or E9-06 [Motor Rated Current (FLA)].
E2-01: Motor Rated Current (FLA)
No.
Name
(Hex.)
E2-01
Motor Rated
Current (FLA)
(030E)
Note:
• If E2-01 < E2-03 [Motor No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].
• When the drive model changes, the display units for this parameter also change.
–0.01 A: 2001 to 2042, B001 to B018, 4001 to 4023
–0.1 A: 2056 to 2082, 4031 to 4060
The value set for E2-01 becomes the reference value for motor protection and the torque limit.
Enter the motor rated current written on the motor nameplate. Auto-Tuning the drive will
automatically set E2-01 to the value input for T1-04 [Motor Rated Current].
E5-03: Motor Rated Current (FLA)
No.
Name
(Hex.)
E5-03
Motor Rated
Current (FLA)
(032B)
Note:
When the drive model changes, the display units for this parameter also change.
• 0.01 A: 2001 to 2042, B001 to B018, 4001 to 4023
• 0.1 A: 2056 to 2082, 4031 to 4060
The drive automatically sets E5-03 to the value input for T2-06 [PM Motor Rated Current] after
you do these types of Auto-Tuning:
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
272
Terminals
D+, D-, AC
PS, AC
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor rated current in amps.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the PM motor rated current (FLA).
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Power Supply Specifications
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
Use the UL Listed class 2 power
supply.
Description
Description
Default
(Range)
Determined by o2-
04, C6-01
(10% to 200% of
the drive rated
current)
Default
(Range)
Determined by o2-
04, C6-01
(10% to 200% of
the drive rated
current)

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis