Wiring
5.5

Ensuring the degree of protection

The measuring system meets all the requirements of IP67 protection. Compliance with the
following points is mandatory following installation in the field or servicing in order to ensure
that IP67 protection is maintained:
• The housing seals must be clean and undamaged when inserted into their grooves. The
seals must be dried, cleaned or replaced if necessary.
• All housing screws and screw caps must be firmly tightened.
• The cables used for connection must be of the specified outside diameter (e.g. M20x1.5,
cable diameter 8 to 12 mm).
• Firmly tighten the cable gland. →  9,  42
• The cables must loop down before they enter the cable glands ("water trap"). This means
that any moisture that may form cannot enter the gland. Install the device so that the cable
glands are not facing upwards. →  9,  42
• Cable glands not used are to be blanked off using the dummy plugs provided.
• Do not remove the grommet from the cable gland.
 9
Connection tips to retain IP67 protection
5.6

Post-connection check

Device condition and specifications
Is the device or cable undamaged (visual inspection)?
Electrical connection
Does the supply voltage match the specifications on the
nameplate?
Do the mounted cables have adequate strain relief?
Are the power supply and signal cables correctly
connected?
Are all the screws terminals sufficiently tightened?
Are all the cable entries installed, tightened and sealed?
Are all the housing covers installed and tightened?
42
Notes
--
Notes
Standard mode and SIL mode: U = 11.5 to 42 V
Visual inspection
→  38
→  36
→  42
→  45
iTEMP TMT162
A0024523
DC
Endress+Hauser