Herunterladen Inhalt Inhalt Diese Seite drucken

Appendix; Limit According To Din Vde 0701-0702:2008 - TESTBOY TV 470 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für TV 470:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Appendix

Appendix

Limit according to DIN VDE 0701-0702:2008-06

PE conductor resistance
Insulation resistance
Insulation resistance
Insulation resistance
Equivalent leakage
current
PE conductor current /
Differential current
Contact current
74
<0.3 Ω to 5 m, above 5 m 0.1 Ω for
each additional 7.5 m cable
PC I
>0.3 MΩ Devices with heater elements
>1 MΩ Devices without heater elements
>2 MΩ touchable conductive parts with-
out PE conductor connections
class-II
>2.0 MΩ
PC III
>0.25 MΩ
PC II
<3.5 mA
PC II
0.25 mA
<3.5 mA
<0.5 mA
The equivalent leakage
current can be halved
with devices that have a
2-pole switch and sym-
metrical capacitive
switching.
>3.5 kW 1 mA/kW