27: output on ERR
Defines the state of the digital output if the controller is in system error: 0 = same
as during programme run / 1 = OFF / 2 = ON
following parameters apply on selection PRC only:
32: process mode
Selects the process state the digital output is indicating: 0=programme run (also
ON during segment 0 and at the end of the firing) / 1=programme run (also ON
during segment 0) / 2=programme run / 3=end of the firing / 4=any loop error /
5=programme HOLD / 6=OFF / 7=ON / 10/11/12=mixer in air
excess/stochiometric/cooling mode / 13=programme continues after power
breakdown / 14=do0.6 and not do0.7 / 15=do0.6 and do0.7 / 16=not do0.6 and
do0.7 / 17=control loop off band / 18=programme interrupted due to off band /
19=any monitored loop error / 20=final temperature matches in all monitored
loops / 21=any monitored loop in control range / 22=any monitored loop out of
control range
following parameters apply on selection EVE only:
42: EVENT number
Digital output operating as programme EVENT number #. This identifier must
match the EVENT number specified in the programme table
43: output on IDLE
Defines the state of the digital output when the controller is IDLE: 0 = OFF / 1 = ON
44: output on ERR
Defines the state of the digital output if the controller is in system error: 0 = same
as during programme run / 1 = OFF / 2 = ON
.
operating instructions bentrup TC20xx V1.9
(value range 0 to 2)
(value range 0 to 18)
(value range 0 to 10)
(value range 0 to 1)
(value range 0 to 1)
Table 4: digital input
Digital inputs provide various options. They can be used to create a process value
depending on the pulse frequency. As well they can be used to control programme
execution in different ways. The optional PLC uses digital inputs too. Note: PLC
provides you with total flexibility of the controller. If you are using the PLC of the
controller you must not do any adjustments in this digital input section since all
features are programmed by PLC networks
.
00: input mode
Action on input activation: 0=programme starts all over again / 1=programme
starts / 2=programme stops 3=ON:programme starts all over again OFF:programme
stops / 4=ON:programme stops OFF:programme stops / 5=programme HOLD
01: signal source
Physical input assigned for the action defined before
.
Table 5: program table
The program table determines the parameters and the sequence to be entered for
each program segment. The first program parameter is always a time followed by a
temperature. Depending on the application the following program segment
parameters are offset temperatures (for multizone kilns), program events etc. The
parameter sequence after the 1st temperature is variable; however, keeping all
program EVENTs togather saves program memory
.
00: value type
Select the kind of value in each column of the programme table:
TIME: Very first column of the programme table to hold the segment time
VAL L: Programme value in the range of 10000 to 10000. Typically used for any
(value range OFF, 0 to 5)
(value range DI0.0 to DI0.2)
(options END, TIME, VAL L,
,
VAL S, EVENT)
33