Complex Configuration Mode Table
TC2010/TC2044/TC2066/TC2088 Configuration Table V1.90
Table 0: misc. adjustments
The following miscellaneous settings determine general operation parameters:
.
00: Segments/Prg
Maximum number of segments per program. Entering a smaller number increases
number of program to be saved in your controller. In most applications a maximum
of 20 segments is suitable. Note: Changing this parameter purges program memory
01: ramp mode(s)
Specifies how to define ramps:
TIME: Ramps entered as segment time
GRAD: Ramps entered as gradient (e.g. 200°C/h)
BOTH: Ramps can be entered as segment time as well as gradient
02: lock programs
Allows locking of all programs to avoid any unauthorized changes
03: communicat. ID
ID of the controller for external communication. Each ID must be unique on the
network. SCADA software (e.g. WinControl) uses this ID to identify controller(s).
04: fctn.on pow.up (TC2044/2066/2088)
Function after power up: 0=IDLE, 1/2=restarting the program if conditions were
met (<1=time limit in seconds/2=.. minutes). 3=automatic program start
28
(value range 2 to 99)
(options TIME, GRAD, BOTH)
(options OFF, ON)
(value range OFF to 62)
(value range 0 to 3)
04: Operating Mode (TC2010)
Determines TC2010 operating mode refer to the manual for details: 0=signal
converter, reading and limiter / 1=setpoint controller / 2=setpoint controller with
adjustable heat up ramp / 3=setpoint controller with adjustable heat up ramp and
dwell / 4=watchdog controller / 5=slave contoller for master/slave operation
.
Table 1: analog input
Specifies the analog input signals for the controller. Analog inputs are used to
connect sensors like thermocouples, resistors, voltage/current signals to the
controller. You can exactly define signal type (voltage, resistance, current) as well
as signal range, signal conversion and correction, unit etc. The most common signal
types are predefined. Each column of the table defines one process value which
are named IN00, IN01 etc. The maximum number of analog input depends on the
hardware.
.
00: input mode
specifies the analog input signal type. Choose the appropriate kind of signal
conversion:
01: average cyc.
Averages the analog input signal. Used to eliminate signal interference as well as to
improove signal steadyness. Setting this option to "1" disables the filter. A higher
setting causes higher smoothening (low pass frequency is 1/n Hz). A setting of 4
suits most applications.
02: units
Specifies the unit of the process value
(value range 0 to 5)
(value range END to RES)
(value range 1 to 11)
(options °C, °F, °K, dg, mV, mA,
O2, CO, %, ev, mb, m³, m³h, kh,
kwh, Pa, AT, lda)
operating instructions bentrup TC20xx V1.9