144 Outside tempera-
ture switch, switch-
off value for non-
occupancy time
145 Outside tempera-
ture switch, switch-
ing differential
146 Selection time
switch
Block "Legionella function"
147 Periodicity of le-
gionella function
148 Time for charging
149 Dwelling time at
legionella setpoint
150 Circulating pump
operation during
legionella function
Block "Switching program 3"
151 Weekday (for
switching program 3)
152 Start of first ON
period
153 End of first ON
period
154 Start of second ON
period
Building Technologies
−5.0 °C
(−35.0...+35.0)
...................
3 °C
(1...20)
...................
3
(1...3)
.........................
1
(0...7)
.........................
05:00
(00:00...24:00)
.........................
30 min
(0...360)
min
................
1
(0 / 1)
.........................
1-7
(1...7)
.........................
06:00
(00:00...24:00)
.........................
22:00
(00:00...24:00)
.........................
--:--
(00:00...24:00)
.........................
74 319 0618 0 a
Function can be provided only
°C
when operating line 141 = 1
Function can be provided only
°C
when operating line 141 = 1
1 = heating program
2 = switching program 2
3 = switching program 3
0 = daily
1...7 = weekly, whereby:
1 = always on Monday
2 = always on Tuesday, etc.
For setpoint of legionella func-
tion, refer to line 30
0 = no impact on circulating
pump
1 = with impact on circulating
pump
1 =
Monday
2 =
Tuesday, etc.
1-7 = entire week
Switching program 3
--:-- = period inactive