Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens RVL481 Installationsanleitung Seite 42

Vorschau ausblenden Andere Handbücher für RVL481:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
38
Time of day
39
Weekday
40
Date
en
41
Year
50
Faults
Building Technologies
00:00...23:59
.........................
Display function
(01.01 ... 31.12)
.........................
(1995...2094)
.........................
Display function
Display example of intercon-
nected plants
10 = error code
2 = segment number (data bus
address)
03 = device number (data bus
address)
74 319 0618 0 a
Hours:Minutes
1 = Monday
2 = Tuesday, etc.
Day.Month (e.g. 02.12 for
nd
2
Dec.)
10 = fault outside sensor
30 = fault flow or boiler tem-
perature sensor
40 = fault flow or boiler tem-
perature sensor (primary
circuit)
42 = fault flow or boiler tem-
perature sensor (secon-
dary circuit)
50 = fault d.h.w. storage tank
temperature sensor /
thermostat 1
52 = fault d.h.w. storage tank
temperature sensor /
thermostat 2
54 = fault flow temperature
sensor for d.h.w.
60 = fault room temperature
sensor
61 = fault room unit
62 = wrong room unit con-
nected
73 = fault collector sensor
81 = short-circuit on data bus
(LPB)
82 = same bus address used
several times
100 = two clock masters on the
data bus (LPB)
17.04.2008
42/276

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis