Settings on the "Heating engineer" level
Press
and
simultaneously for 3 seconds to activate the "Heating engineer" level for
selecting the plant type and the plant-related variables.
Selecting the plant type on operating line 51:
The required plant type must be selected on operating line 51 using buttons
activates all functions required for the respective type of plant and shows the associated operat-
ing lines.
A plant type is comprised of a space heating circuit (6 different types) and a d.h.w. circuit
(5 different types). The 2 types of circuits can be combined in 29 different ways. The following
plant diagrams show all possible combinations.
The controller's operating line 51 only accepts combinations that are possible.
Example of a setting:
51
Plant type
Plant types
A6
Room unit
B1
Flow boiler temperature sensor
B3
Flow temperature sensor for d.h.w.
B31
D.h.w. storage tank temp. sensor / thermostat 1
B32
D.h.w. storage tank temp. sensor / thermostat 2
B5
Room temperature sensor
B6
Collector sensor
B7
Return temperature sensor (primary circuit)
B71
Return temperature sensor (secondary circuit)
B9
Outside sensor
E1
Heat source (boiler / heat exchanger)
Building Technologies
1 = heating circuit type 1
2 = d.h.w. circuit type 2
1−1
(1−0 ... 6−5)
.........................
E2
LPB
K6
M1
M3
M4
M5
N1
Y1
Y3
Y7
74 319 0618 0 a
120 = flow alarm
140 = inadmissible bus address
(LPB) or plant type
and
Type numbers in the following
section
Load (room)
Data bus
Electric immersion heater
Heating circuit pump or circulating pump
Charging pump
Circulating pump
Collector pump
Controller RVL481
Heating circuit valve
Changeover valve
D.h.w. valve
17.04.2008
en
. This
43/276