Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens RVL481 Installationsanleitung Seite 49

Vorschau ausblenden Andere Handbücher für RVL481:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Block "Boiler"
91
Boiler operating
mode
92
Maximum limitation
of boiler tempera-
ture
93
Minimum limitation
of boiler tempera-
ture
94
Switching differen-
tial of boiler
95
Minimum limitation
of burner running
time
96
Release limit for
second burner
stage
97
Reset limit for sec-
ond burner stage
98
Waiting time for
second burner
stage
99
Operating mode
pump M1
Building Technologies
0
(0 / 1)
.........................
95 °C
°C
(25...140)
...................
10 °C
°C
(5...140)
...................
6 °C
°C
(1...20)
...................
4 min
min
(0...10)
................
50 °C×min
°C×min
(0...500)
..........
10 °C×min
°C×min
(0...500)
..........
20 min
min
(0...40)
................
1
(0 / 1)
.........................
74 319 0618 0 a
0 = with manual shutdown
(
key)
1 = with automatic shutdown
(OFF when there is no de-
mand for heat)
No safety function
0 = circulating pump without
shutdown in the case of pro-
tective boiler startup
1 = circulating pump with shut-
down in the case of protec-
tive boiler startup
17.04.2008
en
49/276

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis