Tabelle 4.1.16.3-1 Supported function codes
Code Function
23
Delay Measurement
Response Function Codes
0
Confirm
129
Response
130
Unsolicited Message
1)
Counters of REF 610 can not be cleared using the DNP 3.0 protocol.
Tabelle 4.1.16.3-2 Supported objects
OBJECT
Object
Variation
group
1
0
Binary Input, all variations
1
1
Binary Input
1
2
Binary Input with Status
2
0
Binary Input Change, all
variations
2
1
Binary Input Change without
Time
2
2
Binary Input Change with Time
2
3
Binary Input Change with
Relative Time
10
0
Binary Output, all variations
10
1
Binary Output
10
2
Binary Output with Status
12
0
Control Block, all variations
12
1
Control Relay Output Block
12
2
Pattern Control Block
12
3
Pattern Mask
20
0
Binary Counter, all variations
20
1
32-Bit Binary Counter
Description
Perform propagation delay
measurement
Message fragment confirmation
Response to request message
Spontaneous message without
request
(slave must parse)
Function
Description
Codes
(dec)
1, 20,
21, 22
1, 20,
21, 22
1, 20,
21, 22
1
1
1
1, 7, 8,
20, 21,
22
1, 7, 8,
20, 21,
22
REF 610
Supported
REQUEST
RESPONSE
(master must parse)
Qualifier
Function
Codes
Codes
(hex)
(dec)
00, 01,
129
06, 07,
08,
17,28
00, 01,
129
06, 07,
08,
17,28
00, 01,
129
06, 07,
08,
17,28
06, 07,
08
06, 07,
129,
08
130
06, 07,
129,
08
130
00, 01,
129
06, 07,
08,
17,28
00, 01,
129
06, 07,
08,
17,28
Yes
Yes
Yes
Yes
Qualifier
Codes
(hex)
00, 01,
17, 28
00, 01,
17, 28
00, 01,
17, 28
17, 28
17, 28
00, 01,
17, 28
00, 01,
17, 28
103