Herunterladen Inhalt Inhalt Diese Seite drucken

ABB REF 610 Referenzhandbuch Seite 102

Vorschau ausblenden Andere Handbücher für REF 610:
Inhaltsverzeichnis

Werbung

REF 610
102
Abgangsschutzrelais
Technisches Referenzhandbuch
Tabelle 4.1.16.3-1 Supported function codes
Code Function
3
Select
4
Operate
5
Direct operate
6
Direct operate NO ACK
Freeze Function Codes
7
Immediate Freeze
8
Immediate Freeze NO ACK
9
Freeze and Clear
10
Freeze and Clear NO ACK
11
Freeze with time
12
Freeze with time NO ACK
Application Control Function Codes
13
Cold Restart
14
Warm Restart
15
Initialize Data to Defaults
16
Initialize Application
17
Start Application
18
Stop Application
Configuration Function Codes
19
Save configuration
20
Enable Unsolicited Messages Enable Unsolicited Messages
21
Disable Unsolicited
Messages
22
Assign Class
Time Synchronization Function Codes
Description
Select output point of outstation
Respond with status of control point
Set previously selected output
Respond with status of control point
Set output directly
Respond with status of control point
Set output directly
No response
Copy specified objects to freeze buffer
Respond with status of operation
Copy specified objects to freeze buffer
No response
Copy specified objects to freeze buffer
and clear objects
Respond with status of operation
Copy specified objects to freeze buffer
and clear objects
No response
Copy specified objects to freeze buffer
at specified time
Respond with status of operation
Copy specified objects to freeze buffer
at specified time
No response
Perform desired reset sequence
Respond with a time object
Perform desired partial reset operation
Respond with a time object
Initialize the specified data to default
Respond with status of operation
Set the specified application ready to
be run
Respond with status of operation
Start the specified application to run
Respond with status of operation
Stop the specified application to run
Respond with status of operation
Save configuration
Respond with status of operation
Respond with status of operation
Disable Unsolicited Messages
Respond with status of operation
Assign specified objects to a class
Respond with status of operation
1MRS756033
Supported
No
No
No
No
Yes
Yes
1)
Yes
1)
Yes
No
No
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
Yes