Herunterladen Inhalt Inhalt Diese Seite drucken

Analogausgang; Digitalausgang; Digitaleingang - YOKOGAWA TDLS8000 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für TDLS8000:
Inhaltsverzeichnis

Werbung

Prozessalarme
Parameter
Warning selection
Transmission low warning limit
Pressure low warning limit
Pressure high warning limit
Temperature low warning limit
Temperature high warning limit
Gas1 concentration low warning limit
Gas1 concentration high warning limit
Gas2 concentration low warning limit
Gas2 concentration high warning limit

Analogausgang

Parameter
AO output item
Measurement value at 4mA output
Measurement value at 20mA output
AO hold mode during warning
Preset hold value during warning
Preset hold delay during warning
AO hold mode during fault
Preset hold value during fault
Preset hold delay during fault
AO hold mode during calibration/validation
Preset hold value during calibration/validation
AO hold mode during maintenance
Preset hold value during maintenance
AO hold mode during warm-up
Preset hold value during warm-up

Digitalausgang

Number of output delays for warning and fault
DO output item selection

Digitaleingang

Filter time
DI item selection
Concentration 0[ppm]
Transmission
Temperature
Pressure
Concentration 100[ppm]
Transmission
Temperature
Pressure
Parameter
Parameter
Standardwert
Alle gewählt
Auswahl in Anzeige
20[%]
0 – 100[%]
90[kPa]
0.1 – 10,000[kPa]
110[kPa]
0.1 – 10,000[kPa]
0[deg C]
-273 – 3,000[deg C]
100[deg C]
-273 – 3,000[deg C]
10[ppm]
0 – 1E6[ppm]
900,000[ppm]
0 – 1E6[ppm]
10[ppm]
0 – 1E6[ppm]
900,000[ppm]
0 – 1E6[ppm]
Standardwert
Anwender-
einstellungen
Concentration 1
0[%]
0[deg C]
0[kPa]
100[%]
100[deg C]
0.1[kPa]
Non-Hold
3.0[mA]
0
Preset hold
3.0[mA]
0
Preset hold
3.8[mA]
Preset hold
3.8[mA]
Preset hold
3.8[mA]
Standardwert
0
0 – 100
Alle gewählt
Auswahl in Anzeige
Standardwert
0.5[s]
Auswahl in Anzeige
Disable
Auswahl in Anzeige
IM 11Y01D01-01D-E
6-21
Min. – Max.
Min. – Max.
Auswahl in Anzeige
-1E7 – 1E7[ppm]
-1E7 – 1E7[%]
-1E7 – 1E7[deg C]
-1E4 – 1E4[kPa]
-1E7 – 1E7[ppm]
-1E7 – 1E7[%]
-1E7 – 1E7[deg C]
-1E4 – 1E4[kPa]
Auswahl in Anzeige
3.0 – 21.6[mA]
0 – 5
Auswahl in Anzeige
3.0 – 21.6[mA]
0 – 5
Auswahl in Anzeige
3.8 – 20.5[mA]
Auswahl in Anzeige
3.8 – 20.5[mA]
Auswahl in Anzeige
3.8 – 20.5[mA]
Min. – Max.
Min. – Max.
1. Ausgabe: 31. Juli, 2015-00

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis