Instruction
CF-MC Master Controller
Select the Input configuration
• Press the output selection button
configurations
•  LED: The input ports are not used
• 2 LEDs: The Master Controller will switch to cooling mode when the input for
heating/cooling is activated (fig. 2 -
• 3 LEDs: The Master Controller will switch to a fixed set room temperature at 8 °C
for all Room Thermostats when the input for global standby is activated
(fig. 2 -
• 4 LEDs: The Master Controller will switch to cooling mode when the input for
heating/cooling is activated (fig. 2 -
Controller will switch to a fixed set room temperature at 8 °C for all Room
Thermostats when the input for global standby is activated (fig. 2 -
(default)
• Activate selected input configuration by pressing OK
6.4 Relays on more (2-3) Master Controllers
Note: If more Master Controllers are connected to Master Controller #1 in one system their relays for
pump and boiler control should be configured separately !
Activate Relay mode on Master Controller #2/#3 (fig. 23)
• Use the menu selection button
• Activate Relay mode by pressing OK
Select the Relay configuration
• Press the output selection button
figurations
- the output LEDs will be ON – indicated below:
Uses pump and boiler connected to Master Controller #1:
• NO LEDs: The relays are not used (default)
If local manifold and pump are separate:
•  LED: Pump control
• 4 LEDs: Pump control with 2min. start/stop delay
• Activate selected relay configuration by pressing OK
7. Replacing/Resetting the Master Controller

7.1 When?

• If the Master Controller in an existing CF2-system is reset to factory settings or
replaced with another Master Controller, it is necessary to reset all the other
CF2-system components also, in order to be able to re-install them to the reset or
replaced Master Controller, CF-MC !

7.2 How?

Note: The Master Controller should only be "Reset" to factory settings if the normal in- and unin-
stallation procedures can not be followed!
Resetting the Master Controller, CF-MC - fig.23:
• Disconnect the 230V power supply to the Master Controller until the power
LED
is OFF
• Press and hold at the same time the menu selection button
and the output selection button
• Reconnect the 230V power supply to the Master Controller and release the three
buttons when the power LED
• The Master Controller is reset when all output LEDs
Resetting the Room Thermostats, CF-RS, -RP, -RD and -RF – fig 24:
• Remove the Room Thermostat from the back plate
batteries
• Press and hold the push button
VI.UH.K6.1C
8
- the output LEDs will be ON – indicated below:
)
to select the Relay mode. Relay LED
and all the output LEDs
and toggle between the possible Input
)
). In heating mode the Master
. Relay LED
goes ON
and toggle between the possible Relay con-
(Link test) and reconnect the battery
Produced by Danfoss Floor Heating Hydronics 03.2007
, the OK button
are ON
then goes OFF
and disconnect one of the
)
flashes
,