Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze E94A Serie Gerätehandbuch Seite 603

Servo drives 9400 serie
Inhaltsverzeichnis

Werbung

Daten der Anschlussklemmen
Sinusfilter
EZS3−004A200
EZS3−010A200
EZS3−017A200
EZS3−024A200
EZS3−032A200
EZS3−037A200
EZS3−048A200
EZS3−061A200
EZS3−072A200
EZS3−090A200
Sicherheitshinweise für die Installation nach UL/CSA
Original − Englisch
O
Warnings!
Conditions of Acceptability:
ƒ
ƒ
ƒ
EDS94SPP101 DE 11.0
Anschlussklemme
Anschlussquerschnitte
2
[mm
]
[AWG]
0.2 ... 6
24 ... 10
0.5 ... 16
20 ... 6
2.5 ... 25
10 ... 6
2.5 ... 35
12 ... 2
16 ... 50
1/0 ... 6
The products covered by this report are only intended for use with Power
Conversion Equipment (inverters).
Appropriate cooling measures shall be taken based on the power loss data
within the instructions available from the manufacturer.
External wiring material for models with bus bar screw connectors − R/C
(AVLV2), rated 105 °C min., suitable for applied voltage and current. If wiring
material with a lower temperature rating is used, an additional temperature
test at the wiring material has to be conducted in the end use.
l
Zubehör (Übersicht)
Sinusfilter EZS3−xxxA200 4 ... 90 A
Æ
Anzugsdrehmoment
[Nm]
[lb−in]
0.6
5.3
M4
1.5
13.3
2
17.7
M5
3
26.5
8
Filter
PE−Schraube
Anzugsdrehmoment
[Nm]
[lb−in]
2
17.7
3
26.5
603

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

E94b serieE94c serie

Inhaltsverzeichnis