8. TECHNICAL SPECIFICATIONS

Quattro
PowerControl / PowerAssist
Integrated Transfer switch
AC inputs (2x)
Maximum feed through current (A)
Minimum PowerAssist current (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25 °C (VA)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
CHARGER
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary AC output
Multi purpose relay
(5)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60 Hz and to 240V
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
24
Input voltage range: 187-265 VAC
Output voltage: 230 VAC ± 2%
(3)
(4)
Operating temp.: -20 to +50°C (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012)
24/5000/120-50/30
230V
Yes
Yes
Input frequency: 45 – 55 Hz
AC-in-1: 30A
AC-in-2: 30A
AC-in-1: 6,3A
AC-in-2: 4,7A
19 – 33
Frequency
5000
4250
3350
7500
94
30
28,8
27,6
26,4
120
4
yes
Max load: 16A Switches off when in inverter mode
Yes
a - g
Four M8 bolts (2 plus and 2 minus connections)
Screw terminals 13mm² (6 AWG)
30
444 x 328 x 240
EN 60335-1, EN 60335-2-29
EN55014-1, EN 55014-2, EN 61000-3-3
3) Non linear load, crest factor 3:1
4) At 25 ° C ambient
5) Programmable relay which can be set for general
alarm, DC undervoltage or genset start signal function
AC rating: 230V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
Power factor: 1
50 Hz ± 0,1%
:
Humidity (non condensing) : max 95%
Protection: IP 21