To verify the temperature outputs, proceed as follows:
Apply direct voltage between 1 and 2 V (e.g. a 1.5 V dry battery) to input "T1".
Never apply any voltage exceeding 2 V!
Observe correct polarity. Connect the battery's minus pole to the left clamp and the
plus pole to the middle one.
If you connect the temperature sensor, plus/+ (white) must be connected to the
temperature inputs' left screw clamp, the signal "T1" (red) to the middle one and GND/
minus/- (black) to the right screw clamps.
• The control software status window must display a temperature in excess of 50 °C and the
message "SMS sent" must appear; the message text "Alarm Temp1 = xxC" must be sent to
the mobile phone by SMS.
• Choose the features applicable for your configuration in the control software under
"4 temperature outputs".
• Determine who is to be informed how in case of a message as described in the previous
examples (e.g. "output INCALL").
• Send the new configuration to the GSM module by clicking the button "Send".
To control devices (e.g. a ventilator), connect the respective temperature outputs of
the GSM module to the external devices. For this, connect the temperature outputs
under your own discretion (observe permissible operating voltages, see "Technical
Data") or install additional relays (Conrad item no. 502892) or relay PCBs (Conrad
item no. 585498). Also observe the notes in these operating instructions, chapter 14
"Temperature Inputs T1 and T2".
If only a single temperature sensor is connected, this sensor must be connected to
input "T1". If two temperature sensors are connected, the threshold value excesses
of "T1" and "T2" are indicated by SMS.