Herunterladen Inhalt Inhalt Diese Seite drucken

PR Elecronics 9116 Handbuch Seite 45

Vorschau ausblenden Andere Handbücher für 9116:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

isolation:
Input to any ................................................. 300 VAC double / reinforced isolation
Output relay to analogue output ................. 150 VAC double/reinforced or
Analogue output to supply .......................... 300 VAC double/reinforced isolation
Status relay to supply ................................. 150 VAC double/reinforced or
RtD, linear resistance and potentiometer input:
Input
type
Pt100
Ni100
Linear resist.
Potentiometer
Input for RTD types:
Pt10*, Pt20*, Pt50*, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000
Effect of sensor cable resistance
(3- / 4-wire), RTD ......................................... < 0.002 Ω / Ω
Sensor error detection, RTD ....................... Programmable ON / OFF
Short circuit detection, RTD ........................ Yes
Cable resistance per wire (max.), RTD ........ 50 Ω
Sensor current, RTD .................................... Nom. 0.2 mA
* No short circuit detection for Pt10, Pt20 and Pt50
* No short circuit detection for Lin. R_0%≤ app. 18 Ω
tC input:
Type
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
Min.
Max.
value
value
-200°C
+850°C
-60°C
+250°C
0 Ω
10000 Ω
10 Ω
10000 Ω
Min.
Max.
value
value
+0°C
+1820°C
-100°C
+1000°C
-100°C
+1200°C
-180°C
+1372°C
-200°C
+900°C
-180°C
+1300°C
-50°C
+1760°C
-50°C
+1760°C
-200°C
+400°C
-200°C
+600°C
0°C
+2300°C
0°C
+2300°C
-200°C
+800°C
9116 - Product Version 9116-001
300 VAC basic isolation
300 VAC basic isolation
Standard
IEC60751
DIN 43760
-
-
Standard
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
43

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

9116v101-in1031

Inhaltsverzeichnis