Herunterladen Inhalt Inhalt Diese Seite drucken

PR Elecronics 9116 Handbuch Seite 153

Vorschau ausblenden Andere Handbücher für 9116:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

LERBAKKEN 10, 8410 ROENDE DENMARK
Hazardous Classified Location
Class I / II / III, Division 1, Group A,B,C,D,E,F,G
Class I Zone 0 / 1 / 2 Group IIC, IIB, IIA or
Class I Zone 20 / 21
+
4-20 mA
T
-
Loop-powered
transmitter
Module 9116B 1/2
Terminal 54-52
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
900 mW
Ci
3 nF
Li
2 μH
Module 9116B1
Term. 54-52; 51-52
Uo, Voc
28 V
Io, Isc
93 mA
Po
650 mW
Module 9116B2
Terminal 52-54
Uo, Voc
21.4 V
Io, Isc
93 mA
Po
650 mW
Revision date:
2010-02-12
-20 ºC ≤Ta ≤ +60ºC
54
53
52
51
44
43
42
41
54
53
52
51
44
43
42
41
Group
Co
80 nF
IIC or A,B
640 nF
IIB or C,E,F
2.1 μF
IIA or D,G
Group
Co
0.16 μF
IIC or A,B
1.13 μF
IIB or C,E,F
4.15 μF
IIA or D,G
Version Revision
V5 R0
Unclassified Location
Hazardous Classified Location
Class I, Division 2 Group A,B,C,D T4
Class I, Zone 2, Group IIC, IIB, IIA T4
4501
34
33
32
31
14
13
12
11
9116
Power Rail
4501
34
33
32
31
14
13
12
11
9116
Power Rail
Lo
Lo/Ro
4 mH
54 μH/Ω
16 mH 218 μH/Ω
32 mH 436 μH/Ω
Lo
Lo/Ro
4 mH
54 μH/Ω
16 mH 218 μH/Ω
32 mH 436 μH/Ω
Prepared by:
9116QF01
or
Status relay, terminal (33,34)
Non hazardous area installation
Voltage max:
125 VAC / 110 VDC
Power max:
62.5 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC
Zone 2 installation:
Voltage max:
32 VAC/ 32 VDC
Power max:
16 VA / 32 W
Current max:
0.5 A AC / 1 A DC
Relay output, terminal (13,14)
Non hazardous area installation
Voltage max:
250 VAC / 30 VDC
Power max:
500 VA / 60 W
Current max:
2 A AC / 2 ADC
Zone 2 installation
Voltage max:
32 VAC / 30 VDC
Power max:
64 VA / 60 W
Current max:
2 A AC / 2 ADC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
253 V max. 400 Hz
m:
PB
Page:
3/4

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

9116v101-in1031

Inhaltsverzeichnis