Herunterladen Inhalt Inhalt Diese Seite drucken

Atex Installation Drawings, Uk, Fr, De, Dk - PR Elecronics 9116 Handbuch

Vorschau ausblenden Andere Handbücher für 9116:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

atEX installation Drawings, UK, FR, DE, DK

LERBAKKEN 10, 8410 ROENDE DENMARK
9116
For safe installation of 9116B the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
4501
For installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics' modules. It is important
that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
ATEX Certificate: .........................................................................KEMA 10 ATEX 0053 X
Marking:.......................................................................................
Standards
Hazardous area
Zone 0,1,2, 20, 21, 22
+
+
T
+
-
-
Loop
V
4- wire
3- wire
2- wire
Potm . 2
Potm . 3
Potm . 1
RTD / LinR
Revision date:
2010-02-12
ATEX Installation drawing
EN 60079-0 : 2006, EN 60079-11 : 2007, EN 60079-15 : 2005
EN 60079-26 : 2007, EN 61241-0 : 2006, EN 61241-11 : 2006
Non Hazardous area
or Zone 2
-20 ≤Ta ≤ +60ºC
54
53
52
+
-
51
mA
44
43
42
-
+
41
TC
Power Rail
Version Revision
V5 R0
4501
34
33
32
31
14
13
12
11
9116
Prepared by:
9116QA01
II 3 G Ex nA nC T4
II (1) G [Ex ia] IIC/IIB/IIA
II (1) D [Ex iaD]
Status relay, terminal (33,34)
Non hazardous area installation
Voltage max:
125 VAC / 110 VDC
Power max:
62.5 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC
Zone 2 installation:
Voltage max:
32 VAC/ 32 VDC
Power max:
16 VA / 32 W
Current max:
0.5 A AC / 1 A DC
Relay output, terminal (13,14)
Non hazardous area installation
Voltage max:
250 VAC / 30 VDC
Power max:
500 VA / 60 W
Current max:
2 A AC / 2 ADC
Zone 2 installation
Voltage max:
32 V AC / 30 VDC
Power max:
64 VA / 60 W
Current max:
2 A AC / 2 ADC
(
terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
: 253 V; max 400 Hz
m
PB
Page:
1/4

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

9116v101-in1031

Inhaltsverzeichnis