-- Ensure that the refrigeration system is earthed prior to charging the system with
refrigerant.
-- Label the system when charging is complete (if not already).
-- Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure-tested with the appropriate
purging gas. The system shall be leak-tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out prior to leaving the site.
16. Decommissioning:
Before carrying out this procedure, it is essential that the technician is completely
familiar with the equipment and all its details. It is recommended good practice that
all refrigerants are recovered safely. Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required prior to reuse of
reclaimed refrigerant. It is essential that electrical power is available before the
task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
- mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
- all personal protective equipment is available and being used correctly;
- the recovery process is always supervised by a competent person;
- recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate according to manufacturer's
instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
- 21 -
Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rt135cw4Rt150cw4

Inhaltsverzeichnis