5.3
FLUE CONNECTION (FIG. 5.3)
GB
The flue must be sized in accordance with the
provisions of UNI EN 13384-1.
Seal the fittings well and make sure that the flue pipe
fitting is inserted so that the flue cross-section is not
reduced.
If the draught is too strong, we suggest installing a
smoke regulator on the flue pipe fitting (adjustable on
the elbow), essential when draught exceeds 20 PA.
If the wall behind the stove is made of wood or other
combustible material, it will have to be insulated well
and there should be no combustible material for a
radius of at least 20 cm from the flue fitting hole.
Imperfect sealing may let air get through to the flue
which will result in a reduction of the stove draught.
BETTY THERMO
5.3
ANSCHLUSS AN DEN KAMIN (ABB. 5.3)
Die Bemessung des Kamins muss unter Beachtung
der Richtlinie DIN EN 13384-1 erfolgen.
Die Anschlussstutzen gut abdichten und darauf
achten, dass das Einsatzrohr so in den Kamin
gesteckt ist, dass es den Querschnitt des Kamins
nicht reduziert.
Bei Kaminen mit einem übermäßigem Zug empfiehlt
sich die Montage eines Rauchreglers auf dem
Anschlussrohr des Kamins (auf dem Rohrbogen
einstellbar), bei einem starken Zug über 20 PA ist er
unbedingt erforderlich.
Sollte die Wand, an die der Herd lehnt, mit
brennbarem Holz verkleidet sein, muss für eine
angemessene Verkleidung
und um die Öffnung des Rauchabzugs darf sich in
einem Umfeld von mindestens 20 cm kein brennbares
Material befinden. Eine unvollständige Versiegelung
kann einen Lufteintritt in den Kamin mit darauf
folgendem schwächer werdenden Rauchabzug des
Herds.
cod.
395100020
- 12/2010
D
gesorgt
werden
27
27/60