Installation and Operating Instructions
EN
CHAPTER 7
FUNCTION FOR
INSTALLERS
CO2 Settings
Maximum value
CO2 [ppm]
Threshold CO2
[ppm]
Maximum volume
flow CO2 [m³/h]
Fan unit ELS NFC..
In case of problems with one of the aforementioned points, maintenance must be
carried out according to the instructions in CHAPTER 8.
7.1 Factory settings
Volume-flow
Volume-flow
level 1 [m³/h]
Volume-flow
level 2 [m³/h]
Volume-flow
level 3 [m³/h]
Volume-flow
basic ventilation [m³/h]
Volume-flow
interval mode [m³/h]
Interval-times
Interval-runtime
[min]
Interval-pause-time
[h]
VOC Settings
VOC mode
1400 Maximum value
VOC [VOC]
800 Threshold VOC
[VOC]
60 Maximum volume
flow VOC [m³/h]
7.2 Basic ventilation (continuous and intermittent)
Basic ventilation is the lowest prioritised operating mode. It is interrupted by all
other requests. After an interruption, the basic ventilation restarts. A distinction
is made between continuous and intermittent basic ventilation:
Continuous basic ventilation
With continuous basic ventilation, the fan runs continuously at the set volu-
me-flow (≥15 m³/h).
Intermittent basic ventilation
The volume-flow setting of 7.5 m³/h can only be realised by intermittent opera-
tion of the fan. The fan alternates between active time and pause time, whereby
the basic ventilation mode always starts with the pause time. The fan runs at 15
m³/h during the active time and the fan is off during the pause time.
The control system automatically sets the active and pause times to 30 minutes
each, and these times are not adjustable.
7.3 Manual operation
Manual operation is possible for all variants by activating the switch inputs 1, 2
and 3. The switch inputs are usually switched on or off using a light switch. For
Follow-up-time
35 Follow-up-time
level 1 [s]
60 Follow-up-time
level 2 [s]
100 Follow-up-time
level 3 [s]
15
60
Presence Settings
0
Follow-up-time
P-sensor [min]
0
Maximum volu-
me-flow P-sensor
[m³/h]
Humidity-settings
comfort Dehumidification-mode comfort
250
Maximum value relative
humidity [%]
100
Threshold relative
humidity [%]
60
Maximum volume flow
humidity control [m³/h]
22
Switch-on-delay
45 Switch-on-de-
15
lay level 1 [min]
45 Switch-on-de-
15
lay 2 [min]
45 Switch-on-de-
15
lay level 3 [min]
15
60
90
60
60