17. Technische Daten
17.1 Tabellarische Daten
Isolationskoordination nach IEC 60664-1/IEC 60664-3
Definitonen:
Messkreis (IC1).........................................................................................................................................................(L1/+, L2, L3/-)
Versorgungskreis (IC2)............................................................................................................................................................. A1, A2
Ausgangskreis 1 (IC3) .........................................................................................................................................................11, 12, 14
Ausgangskreis 2 (IC4) .........................................................................................................................................................21, 22, 24
Steuerkreis (IC5)......................................................................................................................................... (E, KE), (X1, ETH, X3, X4)
Bemessungsspannung .....................................................................................................................................................................1000 V
Überspannungskategorie......................................................................................................................................................................... III
Bemessungs-Stoßspannung:
IC1 / (IC2-5) .................................................................................................................................................................................8 kV
IC2 / (IC3-5) .................................................................................................................................................................................4 kV
IC3 / (IC4-5) .................................................................................................................................................................................4 kV
IC4 / IC5 ........................................................................................................................................................................................4 kV
Bemessungs-Isolationsspannung:
IC1 / (IC2-5) .............................................................................................................................................................................1000 V
IC2 / (IC3-5) ...............................................................................................................................................................................250 V
IC3 / (IC4-5) ...............................................................................................................................................................................250 V
IC4 / IC5 ......................................................................................................................................................................................250 V
< 690 V)............................................................................................................................................. 3
Verschmutzungsgrad aussen (U
n
Verschmutzungsgrad aussen (U
>690 < 1000 V)................................................................................................................................ 2
n
Sichere Trennung (verstärkte Isolierung) zwischen:
IC1 / (IC2-5) ............................................................................................................................. Überspannungskategorie III, 1000 V
IC2 / (IC3-5) ............................................................................................................................... Überspannungskategorie III, 300 V
IC3 / (IC4-5) ............................................................................................................................... Überspannungskategorie III, 300 V
IC4 / IC5 ...................................................................................................................................... Überspannungskategorie III, 300 V
Spannungsprüfung (Stückprüfung) nach IEC 61010-1:
IC2 / (IC3-5) ........................................................................................................................................................................ AC 2,2 kV
IC3 / (IC4-5) ........................................................................................................................................................................ AC 2,2 kV
IC4 / IC5 ............................................................................................................................................................................... AC 2,2 kV
Versorgungsspannung
Versorgung über A1/+, A2/-:
Versorgungsspannungsbereich U
...............................................................................................................................AC/DC 24...240 V
s
Toleranz von U
.................................................................................................................................................................. -30...+15 %
S
Maximal zulässiger Eingangsstrom von U
................................................................................................................................... 650 mA
s
Frequenzbereich von U
............................................................................................................................................... DC, 50...400 Hz
s
Toleranz des Frequenzbereichs von U
................................................................................................................................. -5...+15 %
s
Leistungsaufnahme typisch 50/60 Hz............................................................................................................................... ≤ 12 W/21 VA
Leistungsaufnahme typisch 400 Hz................................................................................................................................... ≤ 12 W/45 VA
61
Technische Daten
Versorgung über X1:
Versorgungsspannung U
...............................................................................................................................................................DC 24 V
s
Toleranz von U
.............................................................................................................................................................. DC -20...+25 %
s
Überwachtes IT-System
Netznennspannungsbereich U
...........................................................................................................................................AC 0...690 V
n
.............................................................................................................................................................................................DC 0...1000 V
................................................................................................................................................. AC/DC 0...600 V (für UL Anwendungen)
Toleranz von U
....................................................................................................................................................................AC/DC +15 %
n
Frequenzbereich von U
....................................................................................................................................................DC, 1...460 Hz
n
Max. Wechselspannung U
im Frequenzbereich f
~
Ansprechwerte
Ansprechwert R
(Alarm 1)..............................................................................................................................................1 kΩ...10 MΩ
an1
Ansprechwert R
(Alarm 2)..............................................................................................................................................1 kΩ...10 MΩ
an2
Ansprechunsicherheit (nach IEC 61557-8)...................................................................................profilabhängig, ±15 %, mind. ±1 kΩ
Hysterese.........................................................................................................................................................................25 %, mind. 1 kΩ
Zeitverhalten
bei R
= 0,5 x R
= 10 kΩ) und C
Ansprechzeit t
(R
an
F
an
an
...............................................................................................................................................profilabhängig, typ. 4 s (siehe Diagramme)
Ansprechzeit DC-Alarm bei C
= 1 μF ...................................................................................profilabhängig, typ. 2 s (siehe Diagramm)
e
Anlaufverzögerung T
.......................................................................................................................................................... 0...120 s
Anlauf
Messkreis
Messspannung U
...................................................................................... profilabhängig, ±10 V, ±50 V (siehe Übersicht der Profile)
m
Messstrom I
...............................................................................................................................................................................≤ 403 μA
m
Innenwiderstand R
,Z
.................................................................................................................................................................≥ 124 kΩ
i
i
Zulässige Fremdgleichspannung U
..........................................................................................................................................≤ 1200 V
fg
Zulässige Netzableitkapazität C
................................................................................................................. profilabhängig, 0...1000 μF
e
Messbereiche
Messbereich f
....................................................................................................................................................................... 10...460 Hz
n
Toleranz Messung von f
....................................................................................................................................................±1 % ±0,1 Hz
n
Spannungsbereich Messung von f
...................................................................................................................................AC 25...690 V
n
Messbereich U
(ohne externes Ankoppelgerät) ...............................................................................................................AC 25...690 V
n
...........................................................................................................................................................................................DC 25...1000 V
Spannungsbereich Messung von U
................................................................................................................................... AC/DC > 10 V
n
Toleranz Messung von U
........................................................................................................................................................±5 % ±5 V
n
Messbereich C
........................................................................................................................................................................0...1000 μF
1)
e
Toleranz Messung von C
..................................................................................................................................................±10 % ±10 μF
e
Frequenzbereich Messung von C
...................................................................................................................................DC, 30...460 Hz
e
Min. Isolationswiderstand Messung von C
......................................................abhängig von Profil und Ankopplungsart, typ. > 10 kΩ
e
= 1...10 Hz........................................................... U
n
~ max
= 1 μF nach IEC 61557-8 ..............................................................................
e
iso685-D_D00022_06_M_XXDE/04.2017
= 38 V/Hz² *(1+ f
²)
n