Herunterladen Diese Seite drucken

Helios AIR1 XVP 850 Montage- Und Betriebsvorschrift Seite 101

Zentral-lüftungsgeräte

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
Central ventilation units AIR1 XVP
The room temperature can be adapted when the outside temperature rises. For example, a slightly higher room tem-
perature may be acceptable at higher outside temperatures, or a slightly lower room temperature in cooler weather
conditions. This function is used to conserve energy.
The room temperature setpoint is compensated for depending on the outdoor temperature using a control curve with
8 points.
Example:
Outdoor temp [°C]
Room temp [°C]
-20
-15
-10
-5
0
5
10
15
Temp. control mode
Outd comp room
If cascade control
Max/Min supply setp
Max: XX.X °C
Min: XX.X °C
Outdoor comp setp
-20.0 °C = 25.0 °C
-15.0 °C = 24.0 °C
-10.0 °C = 23.0 °C
Outdoor comp setp
-5.0 °C = 23.0 °C
-0.0 °C = 22.0 °C
-0.0 °C = 20.0 °C
Outdoor comp setp
10.0 °C = 18.0 °C
15.0 °C = 18.0 °C
18
18
23
22
23
23
24
25
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
31
EN
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK

Werbung

loading