Installation and Operating Instructions
EN
Central ventilation units AIR1 XVP
Inbetriebnahme Assistent
211 Commissioning assistant (wizard)
The most important ventilation unit settings can be adjusted using the commissioning assistant (wizard) (except for
adjustment, emergency operation, time/date, timer). The controller will automatically open the commissioning assistant
during the initial commissioning and starts with the language selection.
If the settings are to be subsequently adjusted (except for language selection, time, temperature and ventilation setpo-
ints), the commissioning assistant (wizard) must be called up again.
2111
Menu overview Commissioning assistant (Wizard)
AIR1 XC series
AIR1 XC series
Choose your
Choose your
unit size
unit size
Not applicable
Not applicable
Start
after first
Choose Language
power
English
supply
External 0-10V
control
No
Control function-
Mode
->
Supply air control
SAF CAV setp
Ventilation-
Reduced: 370 m3/h
Mode
Normal: 600 m3/h
Constant air flow
Boost: 750 m3/h
Electrical
EAF CAV setp
Reduced: 370 m3/h
preheater
No
Normal: 600 m3/h
Boost: 750 m3/h
Supply filter type
ePM1 55% (F7)
Extract filter type
ePM10 50% (M5)
After heater type
None
Cooler type
None
Free cooling
(Night cooling)
Yes ->
Sensor-Type
Ventilation on
Rel. Humidity*
demand
CO2/mixed gas (VOC)*
No
*
Menus are only
Accept all settings
visible after
and activate the
the corresponding
application
sensor type has
No
been assigned to an
analog input.
Main-
menu
AIR1 XHP series
AIR1 XVP series
Choose your
Choose your
unit size
unit size
AIR1 XVP 850
Not applicable
***
Different temperature
Supply air temp***
Sub-menus depending on selected
Setp: 22.0 °C
Temperature control mode
Neutral Zone
0.0 °C
outd temp activation
22 °C
Outd temp night
High: 18.0°C
Low: 10.0°C
Room temp min 18.0°C
Hour for start/stop
free cooling
Start: 0
Stop: 7
Time to block heat
output after
free cooling
60 Min
Outdoor sensor
placed in intake
channel
No
Minimal: 80
%
Boost: 100 %
Diff:
16
Stop-time: 2
Std
Minimal: 800 ppm
Boost: 1000 ppm
Diff:
160 ppm
Stop-time: 2
Std
**
26
AIR1 RHP series
AIR1 RH series
Choose your
Choose your
unit size
unit size
Not applicable
Not applicable
Sensor-Type
AI2: Rel. Humidity**
Sensor-Type
AI3: mixed gas (VOC)
Sensor-Type
AI4: CO2
Analog input AI2 not available for air
quality sensors, if temperature-control
mode with room temperature
sensor selected