Installation and Operating Instructions
The submenus of the main menu (Part 2 of 2)
7. Inputs / Outputs
AI
AI1: 0.0 Not used
AI exp3
AI2: 45.5 Humidity
AI exp4
AI3: 0.0 Not used
DI
AI4: 0.0 Not used
UI
Each with arrow to the right
UI exp 3
to view signals at
UI exp 4
inputs / outputs.
AO
Each with arrow to the right
DO
to view signals at
inputs / outputs.
8. Manual / Auto
10. Configuration
Supply temp contr
Inputs / Outputs
Auto
Sensor settings
Manual setting: 100.0
Control function
Fan control
Extra sequenc e Y4
SAF: Auto
Extra sequence Y5
Manual set: 100.0
Heating
Exchanger
Cooling
EAF: Auto
Pump control
Manual set: 100.0
Free cooling
Support control
Fire function
Exchanger
Smoke detector func
Auto
Exchanger deicing
Manual set: 100.0
Exch frost prevent
P1 heating
Cooling recovery
Auto
Min limit dampers
P1 exchanger
Run ind/Motor prot
Auto
Type of actuator
Actuator run time
P1 cooling
Actuator period tim
Auto
Step controllers
Recirculation
Alarm settings
Outdoor air damper
Auto
Communication
Other parameters
System
Exhaust air damper
Auto
Extra sequence Y5
Auto
Manual set: 0.0
Central ventilation units AIR1 XVP
9. Settings
Control temp
Supply air control
Control flow
P-band: 33.0 °C
Alarm settings
I-time: 100.0 s
Restore factory
Frost protection
settings: No
Restore user
settings: No
Save user settings:
Flow control SAF
No
P-band: 2100.0 m3/h
I-time:
Min. output: 0
Flow control EAF
P-band: 2100.0 m3/h
I-time:
Min. output: 0
Alarm limits
Alarm delays
Restore alarm
Service alarm
(Filter alarm)
Time counter set
to zero: No
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
49
Frost protection
Active
Setp shutdown: 25.0C
P-band active: 5.0C
Fast stop at frost-
protection alarm: Yes
60.0 s
%
Sequence with
frost prot
60.0 s
Y1 heating
%
Al del supply air
Control dev : 30 Min
High temp : 120 s
Low temp : 600 s
Al del extract air
high temp : 30 min
Low temp : 30 min
Alarm delay
Frost prot: 2 0 s
Frost risk : 0 s
Alarm delay control
dev pressure
SAF: 30 Min
Alarm delay control
dev pressure
EAF: 30 Min
Low efficiency
30 min
Alarm delay
malfunction
SAF: 600 s
Alarm delay
malfunction
EAF: 600 s
Alarm delay malfunc
P1 heating: 5 s
P1 cooling : 5 s
P1 exchan : 20 s
Filter guard1: 180s
Filter guard2: 180s
Flow switch : 5 s
Frost prot: 0 s
Alarm delay
Deicing DI: 0 s
Fire alarm : 0 s
Ext alarm
: 0 s
Alarm delay
Elec heat
: 0 s
Sensor error : 15 s
Rot sent exch: 20 s
EN
Al lim supply air
Control dev : 5.0 °C
High temp : 35.0 °C
Low temp: 10.0 °C
Al lim extract air
High temp : 35.0 °C
Low temp : 10.0 °C
Control dev
SAF: 50.0 m3/h
Control dev
EAF: 50.0 m3/h
Low efficiency
50.0 %
Service alarm
(Filter alarm)
Time until alarm
activates: 12 months
Alarm limit (X1, Y1)
filter guard1
15.0
Pa at
0
m3/h
Alarm limit (X2, Y2)
filter guard1
118
Pa at
400
m3/h
Alarm limit (X3, Y3)
filter guard1
183.0
Pa at
800
m3/h
Alarm limit (X1, Y1)
filter guard2
15.0
Pa at
0
m3/h
Alarm limit (X2, Y2)
filter guard2
103
Pa at
400
m3/h
Alarm limit (X3, Y3)
filter guard2
172
Pa at
800 m3/h