Central ventilation units AIR1 XVP
22
Shipping
The shipping must be carried out carefully. It is recommended to leave the unit in the original packaging until installation
to avoid possible damages and contamination.
The shipping must be carried out by trained and experienced personnel and the necessary safety precautions should
be taken to prevent overturning and slipping of the device. it should be ensured that the weight is evenly distributed
when shipping the unit.
m
Personal injury and/or material damage due to incorrect shipping!
It must be ensured that the means of transport/lifting is suitable to accommodate to the required weight and
size capacity
– Make sure that the unit is firmly seated before lifting it.
m
Danger due to overhead loads!
Lifting gear, units, cables or tackle could be faulty or damaged
– Never stand beneath suspended loads.
m
Personal injury and/or material damage due to unit tipping over!
Due to the high centre of gravity, the unit can tip over and cause personal injury and material damage
– When transporting the unit, carefully observe its behaviour and stay clear of any possible hazardous areas.
Package dimensions and weights
The dimensions and weight of the individual unit types are shown in the following table.
Material damage due to excessive load!
Before off-loading the units, please ensure that the means of transport/lifting have sufficient capacity for the
required weight
The unit can be transported using a forklift, pallet truck or crane.
m
Personal injury and/or material damage due to the unit falling from the forklift!
– Before transporting the unit, please ensure that the forks of forklift truck are long enough to lift more than the entire
underside of the unit (see Fig.2).
Unit type
No of
packages
AIR1 XVP 850
1
AIR1 XVP 1250
1
AIR1 XVP 1800
1
AIR1 XVP 2500
1
AIR1 XVP 3500
1
– Ensure a symmetrical load distribution before lifting the unit.
– Lift the unit slowly.
H
T
If the unit is transported with a crane, the transportation frame holes in the base frame must be used (see Fig.3).
1. Lead the transportation rods through the holes in the base frame.
2. Secure the transportation rods with the screws.
3. Lead the chain or rope to the end of the transportation rods.
Package dimension
H x W x D (mm)
1750 x 900 x 1550
1910 x 860 x 1750
2050 x 1000 x 1970
2200 x 1040 x 2150
2310 x 1230 x 2350
B
4
Package weight (kg)
248
197
383
456
545