Central ventilation units AIR1 XVP
Temp. control mode
Cascade extract ctrl
Extract air temp.
Setp: XX.X °C
e Outdoor Temperature Dependent Supply or Room Temperature Control
Only possible with the humidity-temp. sensor AIR1/KWL-FTF 0-10V accessory.
Connect the analogue output A2 (temp. signal) of the AIR1/KWL-FTF 0-10V to the analogue input AI2 of the ventilation
unit (see wiring diagram).
If the outside temperature is below the adjustable limit (winter), the outdoor compensated supply air temperature con-
trol will be activated (see b. Outdoor Compensated Supply Air Control). Otherwise (summer), the cascade room tem-
perature control will be activated (see c. Cascade Room Temperature Control).
Temp. control mode
Room/Supply air
Supply air temp.
Setp: XX.X °C
Room temp.
Setp: XX.X °C
Outdoor temp for
control mode change
XX.X °C
f Outdoor Temperature Dependent Supply or Extract Temperature Control
If the outside temperature is below the adjustable limit (winter), the outdoor compensated supply air temperature con-
trol will be activated (see b. Outdoor Compensated Supply Air Control). Otherwise (summer), the cascade extract air
temperature control will be activated (see d. Cascade Extract Air Temperature Control).
Temp. control mode
Extract/Supply air
Supply air temp.
Setp: XX.X °C
Extract air temp
Setp: XX.X °C
Outdoor temp for
control mode change
XX.X °C
g Outdoor Temperature Dependent Room Temperature Control
Only possible with the humidity-temp. sensor AIR1/KWL-FTF 0-10V accessory.
Connect the analogue output A2 (temp. signal) of the AIR1/KWL-FTF 0-10V to the analogue input AI2 of the ventilation
unit (see wiring diagram).