Helios AIR1 XVP 850 Montage- Und Betriebsvorschrift Seite 81

Zentral-lüftungsgeräte

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
NOTE
ATTENTION
Central ventilation units AIR1 XVP
The following circuit breakers are recommended:
AIR1 XVP
Phase
Type
Circuit breakers (A)
The units are designed to comply with the respected standards' leakage current limits however because of the
building structure the leakage current may differ from the limits
The table below contains the RCD type and rated residual current based on the designed limit leakage current of each
unit:
Unit type
AIR1 XVP 850
AIR1 XVP 1250
AIR1 XVP 1800
AIR1 XVP 2500
AIR1 XVP 3500
Further information on the power supply connection of accessory components can be found in the installation and
operating instructions for the respective accessory component.
291 Fixing the main switch
The main switch is part of the scope of delivery and is included in the accessory pack (see chap. 2.1.1 "Receipt"
For series AIR1-XVP 850 - 1800, the main switch (➊) is mounted on top.
For series AIR1-XVP 2500/3500, the main switch (➋) is side-mounted on the right or left, on the front or rear.
AIR1 XVP 850-1800
1
The main switch must be fixed as follows for units AIR1 XVP.. :
1. Unlock and open the doors with the key included in the scope of delivery (see Fig.19).
850
1250
1800
~1 / ~3
~1 / ~3
~3
C
C
C
20/3x16
20/3x20
32
RCD type
Current RCD (mA)
B or B+
B or B+
B or B+
B or B+
B or B+
AIR1 XVP 2500/3500
2
11
2500
3500
~3
~3
C
C
40
50
Leakage current (mA)
30.0
5.88
30.0
8.24
30.0
13.04
30.0
13.27
300.0
20.15
EN
Fig18
Fig19