STEP 8: Run the motor
This step will provide instructions on how to set-up the basic drive parameters, perform an auto-tune and
run the motor in analog input terminal mode or keypad mode.
Action
Power Up
Ensure:
Minimum and
Enter:
maximum
speed
Accel and
Enter:
Decel rates
Motor
nameplate
details
Ready to autotune
Autotune
The drive is able to perform either a stationary or a rotating autotune. The motor must be
at a standstill before any autotune is enabled and disconnected from the load for a
rotating autotune.
To perform an autotune:
EN
Ready to run (Analog input terminal mode by default)
Run
The drive is now ready to run the motor. Close enable (C200) or Safe Torque Off (C300)
and the Run Forward or Run Reverse terminals.
Increasing
and
Changing the selected Analog frequency reference will increase and decrease the speed
decreasing
of the motor.
speed
Stopping
To stop the motor by following the selected deceleration rate, open either the run forward
or run reverse terminals. If the enable terminal is opened while the motor is running, the
drive output is immediately disabled and the motor will coast to a stop.
Ready to run (Keypad mode)
Run
The drive is now ready to run the motor. Set Pr 05 to 'PAd'. Close enable (C200) or Safe
Torque Off (C300).
Press the start key
Increasing
and
Press the up and down keys
decreasing
speed
Stopping
Press the Stop/Reset key
C200/C300 Step By Step Guide
The drive displays: inh (Enable terminal(s) is open)
Minimum speed Pr 01 (Hz)
Maximum speed Pr 02 (Hz)
Acceleration rate Pr 03 (s)
Deceleration rate Pr 04 (s)
Motor rated current in Pr 06 (Amps)
Motor rated speed in Pr 07 (rpm / min
Motor rated voltage in Pr 08 (Volts)
Motor Rated Power factor (Cos ) in Pr 09
Set Pr 10 to L2.
Go to Pr 38.
Set Pr 38 = 1 for a stationary autotune or set Pr 38 = 2 for a rotating autotune
Close the drive enable signal (apply +24 V to terminal 11 or terminal 31 and 34 on
Commander C300). The drive will display 'rdy'.
Give a Run command (apply +24 V to terminal 12 - Run forward or terminal 13 -
Run reverse. The display will flash 'tuning' while the drive is performing the autotune.
Wait for the drive to display 'inh' and for the motor to come to a standstill.
Remove the drive enable and run signal from the drive.
Detail
IP 55
-1
)
to increase and decrease the speed.
MOT. 3
LS 80 L T
N
9
734570 BJ 002
kg
I cl.F
40 C
S1
V
Hz min
kW cos
A
-1
230 50 2800 0,75 0,83 0,3
3
2
4 4
1
19

Werbung

loading