Siemens SIPROTEC 5 Handbuch Seite 190

Communication protocols
Vorschau ausblenden Andere Handbücher für SIPROTEC 5:

Werbung

IEC 60870-5-104
4.3 Interoperabilität
Process Information in Control Direction
(Station-specific parameter, mark each Type ID X if it is only used in the standard direction, R if only used in
the reverse direction, and B if used in both directions)
<45> = Single command
<46> = Double command
<47> = Regulating step command
<48> = Set point command, normalized value
<49> = Set point command, scaled value
<50> = Set point command, short floating-point value
<51> = Bitstring of 32 bit
<58> = Single command with time tag CP56Time2a
<59> = Double command with time tag CP56Time2a
<60> = Incremental command with time tag CP56Time2a
<61> = Set point command, normalized value with time tag CP56Time2a
<62> = Set point command, scaled value with time tag CP56Time2a
<63> = Set point command, short floating-point value with time tag CP56Time2a
<64> = Bitstring of 32 bit with time tag CP56Time2a
Either the ASDUs of the set from <45> to <51> or of the set from <58> to <64> are used.
System Information in Monitor Direction
(Station-specific parameter, mark X if it is only used in the standard direction, R if only used in the reverse
direction and B if used in both directions)
<70> = End of initialization
System Information in Control Direction
(Station-specific parameter, mark each Type ID X if it is only used in the standard direction, R if only used in
the reverse direction, and B if used in both directions)
<100> = Interrogation command
<101> = Counter interrogation command
<102> = Read command
<103> = Clock synchronization command
<104> = Test command (not supported)
<105> = Reset process command
<106> = Delay acquisition command (not supported)
<107> = Test command with time tag CP56time2a
Parameter in Control Direction
(Station-specific parameter, mark each Type ID X if it is only used in the standard direction, R if only used in
the reverse direction, and B if used in both directions)
<110> = Parameter of measured value, normalized value
<111> = Parameter of measured value, scaled value
190
SIPROTEC 5, Communication Protocols, Handbuch
C53000-L1800-C055-H, Ausgabe 07.2023
C_SC_NA_1
C_DC_NA_1
C_RC_NA_1
C_SE_NA_1
C_SE_NB_1
C_SE_NC_1
C_BO_NA_1
C_SC_TA_1
C_DC_TA_1
C_RC_TA_1
C_SE_TA_1
C_SE_TB_1
C_SE_TC_1
C_BO_TA_1
M_EI_NA_1
C_IC_NA_1
C_CI_NA_1
C_RD_NA_1
C_CS_NA_1
C_SE_NB_1
C_RP_NA_1
C_CD_NA_1
C_TS_TA_1
P_ME_NA_1
P_ME_NB_1