Communication protocols
Vorschau ausblenden Andere Handbücher für SIPROTEC 5:

Werbung

Selection of Standard ASDUs
Process Information in Monitor Direction
(Station-specific parameter, mark each Type ID X if it is only used in the standard direction, R if only used in
the reverse direction, and B if used in both directions)
<1> = Single-point information
<2> = Single-point information with time tag (not supported)
<3> = Double-point information
<4> = Double-point information with time tag (not supported)
<5> = Step position information
<6> = Step position information with time tag (not supported)
<7> = Bitstring of 32 bit
<8> = Bitstring of 32 bit with time tag (not supported)
<9> = Measured value, normalized value
<10> = Measured value, normalized value with time tag (not supported)
<11> = Measured value, scaled value
<12> = Measured value, scaled value with time tag (not supported)
<13> = Measured value, short floating-point value
<14> = Measured value, short floating-point value with time tag (not supported)
<15> = Integrated totals
<16> = Integrated totals with time tag (not supported)
<17> = Event of protection equipment with time tag (not supported)
<18> = Packed start events of protection equipment with time tag (not supported)
<19> = Packed output circuit information of protection equipment with time tag (not
supported)
<20> = Packed single-point information with status change detection
<21> = Measured value, normalized value without quality descriptor
<30> = Single-point information with time tag CP56Time2a
<31> = Double-point information with time tag CP56Time2a
<32> = Step position information with time tag CP56Time2a
<33> = Bitstring of 32 bit with time tag CP56Time2a
<34> = Measured value, normalized value with time tag CP56Time2a
<35> = Measured value, scaled value with time tag CP56Time2a
<36> = Measured value, short floating-point value with time tag CP56Time2a
<37> = Integrated totals with time tag CP56Time2a
<38> = Event of protection equipment with time tag CP56Time2a
<39> = Packed start events of protection equipment with time tag CP56Time2a
<40> = Packed output circuit information of protection equipment with time tag
CP56Time2a
The ASDUs of the set from <30> to <40> are used.
SIPROTEC 5, Communication Protocols, Handbuch
C53000-L1800-C055-H, Ausgabe 07.2023
IEC 60870-5-104
4.3 Interoperabilität
M_SP_NA_1
M_SP_TA_1
M_DP_NA_1
M_DP_TA_1
M_ST_NA_1
M_ST_TA_1
M_BO_NA_1
M_BO_TA_1
M_ME_NA_1
M_ME_TA_1
M_ME_NB_1
M_ME_TB_1
M_ME_NC_1
M_ME_TC_1
M_IT_NA_1
M_IT_TA_1
M_EP_TA_1
M_EP_TB_1
M_EP_TC_1
M_SP_NA_1
M_ME_ND_1
M_SP_TB_1
M_DP_TB_1
M_ST_TB_1
M_BO_TB_1
M_ME_TD_1
M_ME_TE_1
M_ME_TF_1
M_IT_TB_1
M_EP_TD_1
M_EP_TE_1
M_EP_TF_1
189