Siemens SIPROTEC 5 Handbuch Seite 186

Communication protocols
Vorschau ausblenden Andere Handbücher für SIPROTEC 5:

Werbung

IEC 60870-5-104
4.3 Interoperabilität
4.3
Interoperabilität
Übersicht
4.3.1
Dieses Kapitel ist für Experten im Bereich IEC 60870-5-104 vorgesehen und wird nicht in andere Sprachen
übersetzt. Es enthält eine Interoperabilitätsliste für die Funktionen, die von IEC 60870-5-104 unterstützt
werden.
This companion standard presents sets of parameters and alternatives from which subsets must be selected
to implement particular telecontrol systems. Certain parameter values, such as the choice of "structured"
or "unstructured" fields of the INFORMATION OBJECT ADDRESS of ASDUs represent mutually exclusive alterna-
tives. This means that only one value of the defined parameters is admitted per system. Other parameters,
such as the listed set of different process information in command and in monitor direction allow the
specification of the complete set or subsets, as appropriate for given applications. This clause summarizes the
parameters of the previous clauses to facilitate a suitable selection for a specific application. If a system is
composed of equipment stemming from different manufacturers, it is necessary that all partners agree on the
selected parameters.
The interoperability list is defined as in IEC 60870-5-101 and extended with parameters used in this standard.
The text descriptions of parameters which are not applicable to this companion standard are strike-through
(corresponding check box is marked black).
Note: In addition, the full specification of a system may require individual selection of certain parameters
for certain parts of the system, such as the individual selection of scaling factors for individually addressable
measured values.
Function or ASDU is not used
Function or ASDU is used as standardized (default)
Function or ASDU is used in reverse mode
Function or ASDU is used in standard and reverse mode
The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.
A black check box indicates that the option cannot be selected in this companion standard.
4.3.2
System or Device
(System parameter, indicate the station function by marking one of the following with X)
Controlled station definition (Slave)
System definition
Controlling station definition (Master)
4.3.3
Network Configuration
4.3.3.1
Not Realized Features
(Network-specific parameter, all configurations that are used are to be marked X)
Point-to-point
Multiple point-to-point
186
Multipoint
Multipoint-star
SIPROTEC 5, Communication Protocols, Handbuch
C53000-L1800-C055-H, Ausgabe 07.2023