Encoder Interface Resolver / HTL Input
4.
Start-up
After the installation or exchange of an encoder interface some adjustments of the inverter/
servo software have to be done before operation:
• Switch on inverter
• Select application mode
• Select parameter Ec.00 and control whether value „7: resolver interface" is entered.
The displayed value has to be confirmed by „ENTER" in any case.
• Select parameter Ec.10 and control whether value „15: inc. input with alarm 24V HTL
is entered.
• Select parameter Ec.11 for channel 2 and adjust increments per revolution
• Select Ec.42 (in the past Ec.20) and adjust the encoder breakage recognition depen-
dent on the case of operation.
5.
Error Messages
Error messages and their meaning are described in the inverter documentation.
GB-14
For safety reasons a power-on-reset must always be executed after error
„E.EnC".