5.1

Measurement input

Symbol
Notes
C111
Transducer/probe (measurement input)
C112
Unit of measurement (°C/°F)/decimal places in display
SCL
Start/end value of value range
for standard signals and resistance transmitter
Example: 0—20 mA
SCH
OFFS
Correction of the actual value
Actual-value correction permits adjusting a measured value upwards or downwards by a
programmable value (offset). For a 2-wire circuit, lead compensation can thus be implemented
in the software (for Pt100 probes, for example, a lead resistance of 0.39
temperature deviation of 1°C).
Examples:
measured value
294.7
295.3
dF
Filter time constant (damping), for adapting the digital input filter (0sec = filter off).
The value range of
dF
if
is large:
SCL
20— 200°C:
offset
displayed value
+ 0.3
295.0
- 0.3
295.0
dF
is 0.0 — 100.0sec; factory setting: 0.6sec.
- high damping of interference signals
- slow reaction of the actual-value display to changes in the actual value
- low limit frequency (2nd order low-pass filter)
SCH
= 20 /
= 200
vPage 19
vPage 20
vPage 22
vPage 22
corresponds to a
14