TEST RUN MENU
Element
Optional function
Minimum operation time
to allow the change of
operation mode in auto
rb
cooling/heating mode
with dual set point
Maximum outdoor
temperature to allow
operation mode switch
rC
to heating in auto
cooling/heating with dual
set point
Minimum outdoor
temperature to allow
operation mode switch
rd
to cooling in auto
cooling/heating with dual
set point
Temperature for the
beginning of heating in
rE
setback
24
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
Disabled
00
10 minutes
01
20 minutes
02
30 minutes
03
40 minutes
04
X
50 minutes
05
60 minutes
06
70 minutes
07
80 minutes
08
90 minutes
09
100 minutes
10
110 minutes
11
120 minutes
12
Disabled
00
20.0 ºC
01
21.0 ºC
02
22.0 ºC
03
·
·
·
·
X
·
·
40.0 ºC
21
0.0 ºC
22
1.0 ºC
23
2.0 ºC
24
·
·
·
·
·
·
19.0 ºC
41
Disabled
00
10.0 ºC
01
11.0 ºC
02
12.0 ºC
03
·
·
·
·
·
·
X
40.0 ºC
31
-20.0 ºC
32
-19.0 ºC
33
-18.0 ºC
34
·
·
·
·
·
·
9.0 ºC
61
15.0 ºC
00
16.0 ºC
01
17.0 ºC
02
18.0 ºC
03
19.0 ºC
04
X
10.0 ºC
05
11.0 ºC
06
12.0 ºC
07
13.0 ºC
08
14.0 ºC
09
Setting conditions
This function is used to define a
minimum time of operation in a given
mode, in order to avoid too frequent
changes of operation mode.
Operation mode does not change
until the minimum transition time
passes, even if the room temperature
reaches the setpoint to shift to the
other operation mode.
If outdoor ambient temperature is
higher than rC, there is no mode
transition to heating in automatic
cooling/heating operation mode,
even if room temperature reaches
the setpoint to switch operation mode
from cooling to heating.
If outdoor ambient temperature is
lower than rd, there is no mode
transition to cooling in automatic
cooling/heating operation mode,
even if room temperature reaches
the setpoint to switch operation mode
from heating to cooling.
If room temperature becomes lower
than this setting, indoor unit operation
is resumed in heating mode by the
setback function.
Description