TEST RUN MENU
Element
Optional function
Automatic COOL/HEAT
b8
operation
Locking of fan speed
b9
setting
Not available
bA
Cooling setting
bb
temperature correction
Not used
bC
Not used
bd
Not used
bE
Not used
C1
Not available
C2
Not used
C3
Drain pump operation in
C4
heating mode
Static pressure selection
Models
RPI-FSN5E
RPIM-FSN4E(-DU)
RPI-FSN3(P)E(-f)
Increase of fan speed
during normal operation
(not during heating
thermo OFF)
Models
RCI-FSN4
C5
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPK-FSN(H)3M
RPF(I)-FSN2E
C5
0
1
2
Increase of fan speed at
C6
heating thermo OFF
11
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
Function disabled (factory setting)
00
X
Function enabled
01
Function disabled
00
(factory setting)
X
Function enabled
01
"- -"
X
Not available
permanent
No compensation (factory setting)
00
Setting temperature decreased by
01
O
1 ºC
Setting temperature decreased by
02
2 ºC
00
-
01
00
-
01
00
-
01
00
-
01
"- -"
-
permanent
00
-
01
Function disabled
00
(factory setting)
O
Function enabled
01
Standard static pressure
00
(factory setting)
O
High static pressure
01
Low static pressure
02
Standard
00
(factory setting)
Hi Speed 1
01
O
Hi Speed 2
02
Fan speed setting on the remote controller
High H
High
Hi2
Hi
Hi2
Hi1
Hi2
Hi2
Function disabled
00
(factory setting)
O
Function enabled
01
Setting conditions
This function enables the selection of
Auto cool/heat operation mode. If the
function is not activated, Auto cool/
heat mode cannot be selected on the
remote control switch.
This function prevents the
modification of the fan speed of the
unit from the remote controller and
from central controls, once it has
been selected.
This function decreases the setting
temperature and is used to produce
longer cooling periods.
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
This function is used to activate the
drain pump in heating mode. Only for
models with drain pump.
This function is used to change the
static pressure of the RPI units from
the remote control.
This function is used to change the
fan speed of indoor units installed in
high ceilings.
Medium
Low
Me
Lo
Hi
Me
Hi1
Hi
This function is used to increase
the fan speed when the thermostat
reaches the set temperature in
heating according to the setting of
function C5.
Description

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis