Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi PC-ARFP1E Installations- Und Betriebshandbuch Seite 23

Vorschau ausblenden Andere Handbücher für PC-ARFP1E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 161
TEST RUN MENU
Element
Optional function
KPI: Increase of air
supply volume
E2
Econofresh enthalpy
sensor
Not used
E3
KPI: Pre-cooling / pre-
heating period
E4
Econofresh: CO2 sensor
Not used
E5
Period of indoor fan
operation after cooling
E6
operation stoppage
Not used
E7
Control for stop of the
indoor unit fan during
heating thermo OFF
conditions (with remote
E8
sensor THM-R2AE
connected to the THM4
connector in the indoor
unit PCB)
Intermittent fan
operation in heating stop
E9
Not available for models:
RPF(I)-FSN2E
Not used
EA
Indoor unit fan control
during cooling thermo
Eb
OFF conditions
15
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
Disabled function
00
(factory setting)
Enabled function
01
O
Disabled function
00
(factory setting)
Enabled function
01
00
-
01
Disabled (factory setting)
00
30 minutes
01
60 minutes
02
O
Disabled (factory setting)
00
CO2 sensor
01/02
(required setting E1=00)
00
-
01
Disabled function
00
(factory setting)
O
60 minutes
01
120 minutes
02
00
-
01
Fan operation in Low speed
00
O
Fan stop in thermo OFF conditions.
01
Function disabled
00
(factory setting)
O
Function enabled
01
00
01
-
02
Function disabled
00
(factory setting)
O
Low
01
Slow
02
Setting conditions
This function is used to increase the
air supply pressure in the room.
This function selects the enthalpy
sensor input for Econofresh.
Use at 00 conditions
This function delays unit startup with
energy recovery
This function selects the CO2 gas
sensor input for Econofresh.
Use at 00 conditions
This function prevents the
condensation in the unit by keeping
the fan running after the unit
operation has been turned OFF.
Use at 00 conditions
This function stops the fan to prevent
cold draughts or overheating.
C8 must be set to 01 to use the
E8=01 setting.
The connection of a THM-R2AE
remote temperature sensor to the
THM4 port in the indoor unit PCB
is required. The remote sensor
shall be installed in a proper place
for the correct detection of room
temperature.
(In case that automatic louvre is
set, the louvre will keep operating
in both thermo ON and thermo OFF
condition.)
In case that indoor unit operation is
set OFF by the remote control switch,
under certain conditions the fan is
operated in cycles consisting of 3
minutes of operation at SLow speed
and 30 minutes of stoppage.
Use at 00 conditions
This function decreases speed of the
indoor unit fan during cooling thermo
OFF, to reduce the spread of smells
and humidity.
Description

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis