Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi PC-ARFP1E Installations- Und Betriebshandbuch Seite 18

Vorschau ausblenden Andere Handbücher für PC-ARFP1E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 161
TEST RUN MENU

Optional Setting Items for Function Selection
Element
Optional function
Heating temperature
compensation
Models:
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
b1
RPIM-FSN4E(-DU)
RPK-FSN(H)3M
Heating temperature
compensation
Models:
RPF(I)-FSN2E
Circulation function at
b2
heating thermo OFF
Forced compressor
operation for at least
b3
three minutes
Change of filter cleaning
b4
period
Locking of operation
b5
mode
Locking of setting
b6
temperature
Setting operation mode
b7
as cooling only
10
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
Normal (factory setting)
00
(Setting Temperature + 4 ºC)
No compensation
01
(Setting Temperature)
O
Setting Temperature + 2 ºC
02
Setting Temperature + 3 ºC
03
Setting Temperature + 1 ºC
04
RPF(I)-FSN2E: Normal
(factory setting)
00
(Setting Temperature + 2 ºC)
No compensation
O
01
(Setting Temperature)
Setting Temperature + 2 ºC
02
Function disabled
00
(factory setting)
O
Function enabled
01
Function disabled (factory setting):
Forced compressor operation for at
00
least three minutes can be enabled
or disabled through C7 setting
O
Function enabled:
Forced compressor operation for at
01
least three minutes always occurs
independently of C7 setting
Standard (1200 hours)
00
100 hours
01
1200 hours
O
02
(factory setting)
2500 hours
03
No indication
04
Function disabled
00
(factory setting)
X
Function enabled
01
Function disabled
00
(factory setting)
X
Function enabled
01
Function disabled
00
(factory setting)
X
Function enabled
01
Setting conditions
This function is used to adjust the
temperature difference between the
temperature read by the inlet sensor
and the real room temperature.
This is useful when the inlet air
thermistor is not placed inside the
indoor unit or due to uneven heat
load.
Note:
This function keeps the fan running
during the thermo OFF sequence,
at the fan speed set on the remote
control switch, to prevent the
stratification of air in the room.
This function is used to allow
the setting of C7, to protect the
compressor by preventing it from
being started or stopped for periods
of less than 3 minutes.
This function is used to modify the
period of operation after which the air
filter cleaning indication is shown in
the remote control.
For RPK-FSN(H)3M models, the
factory setting is b4=00: Standard
setting 200 hours.
This function prevents the
modification of the operation mode
of the unit from the remote controller
and from central controls, once it has
been selected.
This function prevents the
modification of the setting
temperature of the unit from the
remote controller and from central
controls, once it has been selected.
This function is used to limit the
operation mode to cooling only and
to prevent heating mode from being
enabled.
Description
The "02", "03", "04" settings may
not be available depending on the
type of indoor unit.
This setting shall be performed
separately for each indoor unit,
even in case that multiple indoor
units are connected to one remote
controller.

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis